Function name
Signal type
Signal name
Description
ETPMMTR:ERRALM
Alarm for reactive reverse
energy exceeding limit in set
interval
FDPSPDIS
Binary inputs
FDPSPDIS:FWD_A
Fault detected in phase
phase A- forward direction
FDPSPDIS:FWD_B
Fault detected in phase
phase B- forward direction
FDPSPDIS:FWD_C
Fault detected in phase
phase C- forward direction
FDPSPDIS:FWD_G
Groundfault detected in
forward direction
FDPSPDIS:NDIR_A
Non-directional fault
detected in phase A
FDPSPDIS:NDIR_B
Non-directional fault
detected in phase B
FDPSPDIS:NDIR_C
Non-directional fault
detected in phase C
FDPSPDIS:NDIR_G
Non-directional pickup,
Phase-Ground
FDPSPDIS:REV_A
Fault detected in phase
phase A- reverse direction
FDPSPDIS:REV_B
Fault detected in phase
phase B- reverse direction
FDPSPDIS:REV_C
Fault detected in phase
phase C- reverse direction
FDPSPDIS:REV_G
Ground fault detected in
reverse direction
FDPSPDIS:TRIP
Trip by pilot communication
scheme logic
FMPSPDIS
Binary inputs
FMPSPDIS:PHG_FLT
Ground fault detected
FMPSPDIS:PICKUP
General pickup signal
FMPSPDIS:PU_A
Fault detected in phase A
FMPSPDIS:PU_B
Fault detected in phase B
FMPSPDIS:PU_C
Fault detected in phase C
GENPDIF
Binary Inputs
GENPDIF:BLKH
Common harmonic block
signal
GENPDIF:INTDIST
Indication that internal fault
has been detected
GENPDIF:OPENCTAL
Open CT Alarm output
signal. Issued after a delay
GENPDIF:TRIP
General, common trip signal
GENPDIF:TRIPRES
Trip signal from restrained
differential protection
GENPDIF:TRIPUNRE
Trip signal from
unrestrained differential
protection
Table continues on next page
1MRK 511 244-UUS A
Section 2
DNP3 data mappings
DNP, 650 series
25
Point list manual