![ABB RELION 650 SERIES Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/abb/relion-650-series/relion-650-series_point-list-manual_3387561037.webp)
Function name
Signal type
Signal name
Description
Binary outputs
STBRREC:COUNT1P
Counting the number of
single-phase reclosing shots
STBRREC:COUNT3P1
Counting the number of
three-phase reclosing shot 1
STBRREC:COUNT3P2
Counting the number of
three-phase reclosing shot 2
STBRREC:COUNT3P3
Counting the number of
three-phase reclosing shot 3
STBRREC:COUNT3P4
Counting the number of
three-phase reclosing shot 4
STBRREC:COUNT3P5
Counting the number of
three-phase reclosing shot 5
STEFPHIZ
Binary inputs
STEFPHIZ:TRIP
Main, common trip
command
STEFPHIZ:TRIP3H
Trip by one of two 3rd
harmonic voltage-based
prot.
STEFPHIZ:TRIP_VN
Trip by fund. freq. neutral
over-voltage protection
SXCBR
Binary inputs
SXCBR:CLOSEPOS
Apparatus closed position
SXCBR:OPENPOS
Apparatus open position
SXCBR:UPD_BLKD
Update of position
indication is blocked
Counters
SXCBR:CNT_VAL
Operation counter value
Double bit indications
SXCBR:POSITION
Apparatus position
indication
SXCBR:TR_POS
Truck position indication
SXSWI
Binary inputs
SXSWI:CLOSEPOS
Apparatus closed position
SXSWI:OPENPOS
Apparatus open position
SXSWI:UPD_BLKD
Update of position
indication is blocked
Counters
SXSWI:CNT_VAL
Operation counter value
Double bit indications
SXSWI:POSITION
Apparatus position
indication
T2WPDIF
Binary inputs
T2WPDIF:BLK2H
General second harmonic
block signal
T2WPDIF:BLK5H
General fifth harmonic block
signal
T2WPDIF:INTFAULT
Indication that internal fault
has been detected
T2WPDIF:TRIP
General trip signal
T2WPDIF:TRIPRES
Trip signal from restrained
differential protection
T2WPDIF:TRIPUNRE
Trip signal from
unrestrained differential
protection
Table continues on next page
1MRK 511 244-UUS A
Section 2
DNP3 data mappings
DNP, 650 series
31
Point list manual