![ABB RELION 650 SERIES Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/abb/relion-650-series/relion-650-series_point-list-manual_3387561049.webp)
OBJECT
REQUEST (Slave will parse)
RESPONSE (Slave will respond with)
2 (write)
07, (limited qty = 1)
50
3
Time and date last
recorded time
2 (write)
07 (limited qty)
51
1
Time and date CTO
129 (response)
130 (unsol. resp)
07 (limited qty)
(qty = 1)
51
2
Unsynchronized time
and date CTO
129 (response)
130 (unsol. resp)
07 (limited qty)
(qty = 1)
52
1
Time delay coarse
129 (response)
07 (limited qty)
(qty = 1)
52
2
Time delay fine
129 (response)
07 (limited qty)
(qty = 1)
60
0
Not defined
60
1
Class 0 data
1 (read)
06 (no range, or all)
60
2
Class 1 data
1 (read)
06 (no range, or all)
07, 08 (limited qty)
20 (enbl. unsol.)
21 (dab.unsol.)
22 (assign class)
06 (no range, or all)
60
3
Class 2 data
1 (read)
06 (no range, or all)
07, 08 (limited qty)
20 (enbl. unsol.)
21 (dab.unsol.)
22 (assign class)
06 (no range, or all)
60
4
Class 3 data
1 (read)
20 (enbl. unsol.)
21 (dab.unsol.)
22 (assign class)
06 (no range, or all)
06 (no range, or all)
07, 08 (limited qty)
80
1
Internal indications
1 (read)
00, 01 (start-stop)
129 (response)
00,01 (start-stop)
2 (write)
3)
00 (start-stop)
index=7
No object (function code only)
13 (cold restart)
No object (function code only)
14 (warm restart)
No object (function code only)
23 (delay meas.)
No object (function code only)
24 (record current
time)
1) A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2 or 3 scans. Default
variations are configurable; however, default settings for the configuration parameters are indicated in the table above.
2) For static (non-change event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28.
Otherwise, static object requests sent with qualifiers 00, 01, 06, 07 or 08 are responded with qualifiers 00 or 01. (For change event
objects, qualifiers 17 or 28 are always responded.)
3) Writings of internal indications are only supported for index 7 (Restart IIn1–7).
1MRK 511 244-UUS A
Section 3
DNP3 protocol implementation
DNP, 650 series
43
Point list manual