Parameter
Values (Range)
Unit
Step
Default
Description
Block Monitoring
0=Not in use
1=Discard events
2=Keep events
0=Not in use
Blocking of Monitoring Direction
Internal Overflow
0=False
1=True
0=False
Internal Overflow: TRUE-System level
overflow occured (indication only)
EC_FRZ
0=False
1=True
0=False
Control point for freezing energy counters
4.2
Monitored data
Table 15:
Protocol diagnostic counters (I3C01 and I3C02)
Attribute
Values (range)
Default Description
Status
False = Communication inactive
True = Communication active
False
Status (read)
Reset counters
False/True
False
True (reset)
Received frames
-1...2147483646
Received frames
Checksum errors
-1...2147483646
Checksum errors
Transmitted frames
-1...2147483646
Transmitted frames
1MRS757647 C
Section 4
IEC 60870-5-103 parameters and diagnostics
620 series
33
Communication Protocol Manual