Frequency
f < StartFrequency
Voltage
start
TRIP
RESTORE
U < IntBlockLevel
block
f > RestoreFreq
BLOCK
OR
Definite timer
or
Voltage based timer
tReset
tDelay
tRestore
restore
IEC16000041-1-en.vsdx
trip
START
BLKTRIP
AND
Start
&
Trip
output
logic
BLKREST
AND
BLKDMAGN
IEC16000041 V1 EN-US
Figure 128:
Simplified logic diagram for SAPTUF
10.1.7
Technical data
M13360-1 v15
Table 140:
SAPTUF technical data
Function
Range or value
Accuracy
Operate value, start function, at symmetrical three
phase voltage
(35.00-75.00) Hz
±2.0 mHz
Operate time, start at f
set
+ 0.02 Hz to f
set
- 0.02 Hz
fn = 50 Hz
Min. = 80 ms
-
Max. = 95 ms
fn = 60 Hz
Min. = 65 ms
Max. = 80 ms
Reset time, start at f
set
- 0.02 Hz to f
set
+ 0.02 Hz
Min. = 15 ms
Max. = 30 ms
-
Operate time, definite time function at f
set
+ 0.02 Hz
to f
set
- 0.02 Hz
(0.000-60.000)s
±0.2% or
±100 ms
whichever
is greater
Table continues on next page
Section 10
1MRK 505 394-UEN A
Frequency protection
272
Line differential protection RED650 2.2 IEC
Technical manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Страница 2: ......
Страница 36: ...30...
Страница 46: ...40...
Страница 232: ...226...
Страница 272: ...266...
Страница 288: ...282...
Страница 306: ...300...
Страница 406: ...400...
Страница 436: ...430...
Страница 502: ...496...
Страница 614: ...608...
Страница 628: ...622...
Страница 644: ...638...
Страница 760: ...754...
Страница 778: ...772...
Страница 814: ...808...
Страница 870: ...864...
Страница 874: ...868...
Страница 924: ...918...
Страница 925: ...919...