Section 11
Secondary system supervision
11.1
Current circuit supervision CCSSPVC
IP14555-1 v5
11.1.1
Identification
M14870-1 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current circuit supervision
CCSSPVC
-
87
11.1.2
Functionality
M12444-3 v10
Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth-fault current and negative-
sequence current functions.
Current circuit supervision (CCSSPVC) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate
input taken from another set of cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to
block protection functions expected to give inadvertent tripping.
11.1.3
Function block
M12436-3 v9
CCSSPVC
I3P*
IREF*
BLOCK
FAIL
ALARM
IEC13000304-1-en.vsd
IEC13000304 V1 EN-US
Figure 133:
CCSSPVC function block
Signal ISIREF must be connected in the configuration.
1MRK 505 394-UEN A
Section 11
Secondary system supervision
Line differential protection RED650 2.2 IEC
283
Technical manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Страница 2: ......
Страница 36: ...30...
Страница 46: ...40...
Страница 232: ...226...
Страница 272: ...266...
Страница 288: ...282...
Страница 306: ...300...
Страница 406: ...400...
Страница 436: ...430...
Страница 502: ...496...
Страница 614: ...608...
Страница 628: ...622...
Страница 644: ...638...
Страница 760: ...754...
Страница 778: ...772...
Страница 814: ...808...
Страница 870: ...864...
Страница 874: ...868...
Страница 924: ...918...
Страница 925: ...919...