The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used). SMAI makes the
information available as a group signal output, phase outputs and calculated residual
output (AIN-output). In situations where AI4-input is used as an input signal the
corresponding information is available on the non-calculated output (AI4) on the
SMAI function block. Connect the signals to the AxRADR accordingly.
For each of the analog signals,
Operation
=
Enabled
means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of
Operation
, and
triggers even if operation is set to
Disabled
. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.
If
Operation
=
Disabled
, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If
Operation
=
Enabled
, waveform (samples) will also be recorded and reported in graph.
The analog signals are presented only in the disturbance recording, but they affect the
entire disturbance report when being used as triggers.
12.3.6.10
Binary signals
Up to 96 binary signals can be selected to be handled by disturbance report. The
signals can be selected from internal logical and binary input signals. A binary signal is
selected to be recorded when:
•
the corresponding function block is included in the configuration
•
the signal is connected to the input of the function block
Each of the 96 signals can be selected as a trigger of the disturbance report (
Operation
=
Operation—>TrigDR =Disabled
). A binary signal can be selected to activate the
yellow (PICKUP) and red (TRIP) LED on the local HMI (
SetLED
=
Disabled/Pickup/
Trip/Pickup and Trip
).
The selected signals are presented in the event recorder, sequential of events and the
disturbance recording. But they affect the whole disturbance report when they are used
as triggers. The indications are also selected from these 96 signals with local HMI
IndicationMask=Show/Hide
.
12.3.6.11
Trigger signals
The trigger conditions affect the entire disturbance report, except the sequential of
events, which runs continuously. As soon as at least one trigger condition is fulfilled, a
complete disturbance report is recorded. On the other hand, if no trigger condition is
1MRK 505 277-UUS C
Section 12
Monitoring
279
Technical Manual
Содержание REB650
Страница 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Страница 2: ......
Страница 34: ...28 ...
Страница 52: ...46 ...
Страница 128: ...122 ...
Страница 150: ...144 ...
Страница 192: ...186 ...
Страница 222: ...216 ...
Страница 360: ...354 ...
Страница 378: ...372 ...
Страница 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Страница 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Страница 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Страница 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Страница 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Страница 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Страница 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Страница 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Страница 446: ...1MRK006502 MC 2 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 440 Technical Manual ...
Страница 447: ...1MRK006502 MC 3 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 441 Technical Manual ...
Страница 448: ...1MRK006502 MC 4 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 442 Technical Manual ...
Страница 449: ...1MRK006502 MC 5 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 443 Technical Manual ...
Страница 450: ...1MRK006502 MC 6 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 444 Technical Manual ...
Страница 451: ...1MRK006502 MC 7 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 445 Technical Manual ...
Страница 452: ...1MRK006502 MC 8 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 446 Technical Manual ...
Страница 453: ...1MRK006502 MC 9 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 447 Technical Manual ...
Страница 454: ...448 ...
Страница 503: ...497 ...