9.1.5
Settings
Table 85:
SDDRFUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Disable/Enable Operation
OpModeSel
Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
-
-
V0I0
Operating mode selection
3V0PU
1 - 100
%VB
1
30
Pickup of residual overvoltage element in %
of VBase
3I0PU
1 - 100
%IB
1
10
Pickup of residual undercurrent element in %
of IBase
3V2PU
1 - 100
%VB
1
30
Pickup of negative sequence overvoltage
element in % of VBase
3I2PU
1 - 100
%IB
1
10
Pickup of negative sequence undercurrent
element in % of IBase
OpDVDI
Disabled
Enabled
-
-
Disabled
Operation of change based function Disable/
Enable
DVPU
1 - 100
%VB
1
60
Pickup of change in phase voltage in % of
VBase
DIPU
1 - 100
%IB
1
15
Pickup of change in phase current in % of
IBase
VPPU
1 - 100
%VB
1
70
Pickup of phase voltage in % of VBase
50P
1 - 100
%IB
1
10
Pickup of phase current in % of IBase
SealIn
Disabled
Enabled
-
-
Enabled
Seal in functionality Disable/Enable
VSealInPU
1 - 100
%VB
1
70
Pickup of seal-in phase voltage in % of VBase
IDLDPU
1 - 100
%IB
1
5
Pickup for phase current detection in % of
IBase for dead line detection
VDLDPU
1 - 100
%VB
1
60
Pickup for phase voltage detection in % of
VBase for dead line detection
Table 86:
SDDRFUF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
1MRK 505 277-UUS C
Section 9
Secondary system supervision
147
Technical Manual
Содержание REB650
Страница 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Страница 2: ......
Страница 34: ...28 ...
Страница 52: ...46 ...
Страница 128: ...122 ...
Страница 150: ...144 ...
Страница 192: ...186 ...
Страница 222: ...216 ...
Страница 360: ...354 ...
Страница 378: ...372 ...
Страница 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Страница 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Страница 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Страница 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Страница 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Страница 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Страница 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Страница 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Страница 446: ...1MRK006502 MC 2 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 440 Technical Manual ...
Страница 447: ...1MRK006502 MC 3 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 441 Technical Manual ...
Страница 448: ...1MRK006502 MC 4 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 442 Technical Manual ...
Страница 449: ...1MRK006502 MC 5 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 443 Technical Manual ...
Страница 450: ...1MRK006502 MC 6 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 444 Technical Manual ...
Страница 451: ...1MRK006502 MC 7 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 445 Technical Manual ...
Страница 452: ...1MRK006502 MC 8 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 446 Technical Manual ...
Страница 453: ...1MRK006502 MC 9 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 447 Technical Manual ...
Страница 454: ...448 ...
Страница 503: ...497 ...