•
It is not mandatory to connect all the inputs of SMAI function. However, it is very
important that same set of three phase analog signals should be connected to one
SMAI function.
•
The sequence of input connected to SMAI function inputs
GRPx_A
,
GRPx_B
,
GRPx_C
and
GRPx_N
should normally represent phase A, phase B, phase C and
neutral currents respectively.
•
It is possible to connect analog signals available as
Ph-N
or
Ph-Ph
to SMAI.
ConnectionType
should be set according to the input connected.
•
If the
GRPx_N
input is not connected and all three phase-to-ground inputs are
connected, SMAI calculates the neutral input on its own and it is available at the
AI3P
and
AIN
outputs. It is necessary that the
ConnectionType
should be set to
Ph-
N
.
•
If any two phase-to-ground inputs and neutral currents are connected, SMAI
calculates the remaining third phase-to-neutral input on its own and it is available
at the
AI3P
output. It is necessary that the
ConnectionType
should be set to
Ph-N
.
•
If any two phase-to-phase inputs are connected, SMAI calculates the remaining
third phase-to-phase input on its own. It is necessary that the
ConnectionType
should be set to
Ph-Ph
.
•
All three inputs
GRPx_x
should be connected to SMAI for calculating sequence
components for
ConnectionType
set to
Ph-N
.
•
At least two inputs
GRPx_x
should be connected to SMAI for calculating the
positive and negative sequence component for
ConnectionType
set to
Ph-Ph
.
Calculation of zero sequence requires
GRPx_N
input to be connected.
•
Negation setting inverts (reverse) the polarity of the analog input signal. It is
recommended that use of this setting is done with care, mistake in setting may lead
to maloperation of directional functions.
Frequency adaptivity
SMAI function performs DFT calculations for obtaining various electrical parameters.
DFT uses some reference frequency for performing calculations. For most of the cases,
these calculations are done using a fixed DFT reference based on system frequency.
However, if the frequency of the network is expected to vary more than 2 Hz from the
nominal frequency, more accurate DFT results can be obtained if the adaptive DFT is
used. This means that the frequency of the network is tracked and the DFT calculation
is adapted according to that.
DFTRefExtOut
and
DFTReference
need to be set appropriately for adaptive DFT
calculations.
DFTRefExtOut
: Setting valid only for the instance of function block SMAI_20_1. It
decides the reference block for external output
SPFCOUT
.
DFTReference
: Reference DFT for the block. This setting decides DFT reference for
DFT calculations.
DFTReference
set to
InternalDFTRef
uses fixed DFT reference
Section 15
1MRK 505 277-UUS C
Basic IED functions
404
Technical Manual
Содержание REB650
Страница 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Страница 2: ......
Страница 34: ...28 ...
Страница 52: ...46 ...
Страница 128: ...122 ...
Страница 150: ...144 ...
Страница 192: ...186 ...
Страница 222: ...216 ...
Страница 360: ...354 ...
Страница 378: ...372 ...
Страница 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Страница 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Страница 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Страница 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Страница 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Страница 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Страница 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Страница 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Страница 446: ...1MRK006502 MC 2 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 440 Technical Manual ...
Страница 447: ...1MRK006502 MC 3 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 441 Technical Manual ...
Страница 448: ...1MRK006502 MC 4 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 442 Technical Manual ...
Страница 449: ...1MRK006502 MC 5 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 443 Technical Manual ...
Страница 450: ...1MRK006502 MC 6 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 444 Technical Manual ...
Страница 451: ...1MRK006502 MC 7 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 445 Technical Manual ...
Страница 452: ...1MRK006502 MC 8 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 446 Technical Manual ...
Страница 453: ...1MRK006502 MC 9 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 447 Technical Manual ...
Страница 454: ...448 ...
Страница 503: ...497 ...