Name
Values (Range)
Unit
Step
Default
Description
IndicationMa15
Hide
Show
-
-
Hide
Indication mask for binary channel 15
TrigLevel16
Trig on 0
Trig on 1
-
-
Trig on 1
Trigger on positive (1) or negative (0) slope
for binary input 16
IndicationMa16
Hide
Show
-
-
Hide
Indication mask for binary channel 16
12.3.6
Operation principle
Disturbance report DRPRDRE is a common name for several functions to supply the
operator, analysis engineer, and so on, with sufficient information about events in the
system.
The functions included in the disturbance report are:
•
Sequential of events
•
Indications
•
Event recorder
•
Trip value recorder
•
Disturbance recorder
shows the relations between Disturbance Report, included functions and
function blocks. Sequential of events , Event recorder and Indications uses information
from the binary input function blocks (BxRBDR). Trip value recorder uses analog
information from the analog input function blocks (AxRADR). Disturbance recorder
DRPRDRE acquires information from both AxRADR and BxRBDR.
Section 12
1MRK 505 277-UUS C
Monitoring
274
Technical Manual
Содержание REB650
Страница 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Страница 2: ......
Страница 34: ...28 ...
Страница 52: ...46 ...
Страница 128: ...122 ...
Страница 150: ...144 ...
Страница 192: ...186 ...
Страница 222: ...216 ...
Страница 360: ...354 ...
Страница 378: ...372 ...
Страница 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Страница 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Страница 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Страница 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Страница 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Страница 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Страница 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Страница 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Страница 446: ...1MRK006502 MC 2 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 440 Technical Manual ...
Страница 447: ...1MRK006502 MC 3 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 441 Technical Manual ...
Страница 448: ...1MRK006502 MC 4 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 442 Technical Manual ...
Страница 449: ...1MRK006502 MC 5 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 443 Technical Manual ...
Страница 450: ...1MRK006502 MC 6 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 444 Technical Manual ...
Страница 451: ...1MRK006502 MC 7 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 445 Technical Manual ...
Страница 452: ...1MRK006502 MC 8 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 446 Technical Manual ...
Страница 453: ...1MRK006502 MC 9 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 447 Technical Manual ...
Страница 454: ...448 ...
Страница 503: ...497 ...