Rate accuracy
In the IED, the rate accuracy at cold start is 100 ppm but if the IED is synchronized for
a while, the rate accuracy is approximately 1 ppm if the surrounding temperature is
constant. Normally, it takes 20 minutes to reach full accuracy.
Time-out on synchronization sources
All synchronization interfaces has a time-out and a configured interface must receive
time-messages regularly in order not to give an error signal (TSYNCERR). Normally,
the time-out is set so that one message can be lost without getting a TSYNCERR, but if
more than one message is lost, a TSYNCERR is given.
15.2.8.3
Synchronization alternatives
Two main alternatives of external time synchronization are available. The
synchronization message is applied either via any of the communication ports of the
IED as a telegram message including date and time or via IRIG-B.
Synchronization via SNTP
SNTP provides a ping-pong method of synchronization. A message is sent from an
IED to an SNTP server, and the SNTP server returns the message after filling in a
reception time and a transmission time. SNTP operates via the normal Ethernet
network that connects IEDs together in an IEC 61850 network. For SNTP to operate
properly, there must be an SNTP server present, preferably in the same station. The
SNTP synchronization provides an accuracy that gives +/- 1 ms accuracy for binary
inputs. The IED itself can be set as an SNTP-time server.
SNTP server requirements
The SNTP server to be used is connected to the local network, that is not more than 4-5
switches or routers away from the IED. The SNTP server is dedicated for its task, or at
least equipped with a real-time operating system, that is not a PC with SNTP server
software. The SNTP server should be stable, that is, either synchronized from a stable
source like GPS, or local without synchronization. Using a local SNTP server without
synchronization as primary or secondary server in a redundant configuration is not
recommended.
Synchronization via IRIG-B
IRIG-B is a protocol used only for time synchronization. A clock can provide local
time of the year in this format. The “B” in IRIG-B states that 100 bits per second are
transmitted, and the message is sent every second. After IRIG-B there numbers stating
if and how the signal is modulated and the information transmitted.
To receive IRIG-B there are one dedicated connector for the IRIG-B port. IRIG-B 00x
messages can be supplied via the galvanic interface, where x (in 00x) means a number
in the range of 1-7.
1MRK 505 277-UUS C
Section 15
Basic IED functions
387
Technical Manual
Содержание REB650
Страница 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Страница 2: ......
Страница 34: ...28 ...
Страница 52: ...46 ...
Страница 128: ...122 ...
Страница 150: ...144 ...
Страница 192: ...186 ...
Страница 222: ...216 ...
Страница 360: ...354 ...
Страница 378: ...372 ...
Страница 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Страница 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Страница 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Страница 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Страница 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Страница 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Страница 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Страница 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Страница 446: ...1MRK006502 MC 2 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 440 Technical Manual ...
Страница 447: ...1MRK006502 MC 3 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 441 Technical Manual ...
Страница 448: ...1MRK006502 MC 4 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 442 Technical Manual ...
Страница 449: ...1MRK006502 MC 5 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 443 Technical Manual ...
Страница 450: ...1MRK006502 MC 6 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 444 Technical Manual ...
Страница 451: ...1MRK006502 MC 7 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 445 Technical Manual ...
Страница 452: ...1MRK006502 MC 8 1 2 ANSI V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 446 Technical Manual ...
Страница 453: ...1MRK006502 MC 9 1 2 ANSI V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 447 Technical Manual ...
Страница 454: ...448 ...
Страница 503: ...497 ...