18.1.7
Current transformer requirements for CTs according to
other standards
SEMOD53771-1 v1
M11623-4 v3
All kinds of conventional magnetic core CTs are possible to use with the IEDs if
they fulfill the requirements corresponding to the above specified expressed as the
rated equivalent limiting secondary e.m.f. E
al
according to the IEC 61869-2
standard. From different standards and available data for relaying applications it is
possible to approximately calculate a secondary e.m.f. of the CT comparable with
E
al
. By comparing this with the required rated equivalent limiting secondary e.m.f.
E
alreq
it is possible to judge if the CT fulfills the requirements. The requirements
according to some other standards are specified below.
18.1.7.1
Current transformers according to IEC 61869-2, class P, PR
M11623-6 v4
A CT according to IEC 61869-2 is specified by the secondary limiting e.m.f. E
ALF
.
The value of the E
ALF
is approximately equal to the corresponding E
al
. Therefore,
the CTs according to class P and PR must have a secondary limiting e.m.f. E
ALF
that fulfills the following:
ALF
alreq
E
max E
EQUATION1383 V4 EN-US
(Equation 46)
18.1.7.2
Current transformers according to IEC 61869-2, class PX, PXR (and
old IEC 60044-6, class TPS and old British Standard, class X)
M11623-14 v5
CTs according to these classes are specified approximately in the same way by a
rated knee point e.m.f. E
knee
(E
k
for class PX and PXR, E
kneeBS
for class X and the
limiting secondary voltage U
al
for TPS). The value of the E
knee
is lower than the
corresponding E
al
according to IEC 61869-2. It is not possible to give a general
relation between the E
knee
and the E
al
but normally the E
knee
is approximately 80 %
of the E
al
. Therefore, the CTs according to class PX, PXR, X and TPS must have a
rated knee point e.m.f. E
knee
that fulfills the following:
(
)
knee
k
kneeBS
al
alreq
E
E
E
U
0.8 maximum of E
»
»
»
>
×
EQUATION2100 V2 EN-US
(Equation 47)
18.1.7.3
Current transformers according to ANSI/IEEE
M11623-22 v6
Current transformers according to ANSI/IEEE are partly specified in different
ways. A rated secondary terminal voltage U
ANSI
is specified for a CT of class C.
U
ANSI
is the secondary terminal voltage the CT will deliver to a standard burden at
20 times rated secondary current without exceeding 10 % ratio correction. There
are a number of standardized U
ANSI
values for example, U
ANSI
is 400 V for a C400
Section 18
1MRK 505 388-UEN B
Requirements
300
Busbar protection REB650 2.2 IEC
Application manual
Содержание REB650
Страница 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Страница 2: ......
Страница 18: ...12...
Страница 28: ...22...
Страница 38: ...32...
Страница 78: ...72...
Страница 96: ...90...
Страница 136: ...130...
Страница 150: ...144...
Страница 156: ...150...
Страница 232: ...226...
Страница 278: ...272...
Страница 298: ...292...
Страница 310: ...304...
Страница 320: ...314...
Страница 321: ...315...