IAngCompY
: Angle compensation to calibrate angle measurements at Y% of Ir,
where Y is equal to 5, 30 or 100.
The following general settings can be set for the
Phase current measurement
(CMMXU).
IAmpCompY
: Amplitude compensation to calibrate current measurements at Y% of
Ir, where Y is equal to 5, 30 or 100.
IAngCompY
: Angle compensation to calibrate angle measurements at Y% of Ir,
where Y is equal to 5, 30 or 100.
The following general settings can be set for the
Phase-phase voltage
measurement
(VMMXU).
UAmpCompY
: Amplitude compensation to calibrate voltage measurements at Y%
of Ur, where Y is equal to 5, 30 or 100.
UAngCompY
: Angle compensation to calibrate angle measurements at Y% of Ur,
where Y is equal to 5, 30 or 100.
The following general settings can be set for
all monitored quantities
included in
the functions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X
in setting names below equals S, P, Q, PF, U, I, F, IL1-3, UL1-3UL12-31, I1, I2,
3I0, U1, U2 or 3U0.
Xmin
: Minimum value for analog signal X set directly in applicable measuring
unit. This forms the minimum limit of the range.
Xmax
: Maximum value for analog signal X. This forms the maximum limit of the
range.
XZeroDb
: Zero point clamping. A signal value less than
XZeroDb
is forced to zero.
Observe the related zero point clamping settings in Setting group N for CVMMXN
(
UGenZeroDb
and
IGenZeroDb
). If measured value is below
UGenZeroDb
and/or
IGenZeroDb
calculated S, P, Q and PF will be zero and these settings will override
XZeroDb
.
XRepTyp
: Reporting type. Cyclic (
Cyclic
), amplitude deadband (
Dead band
),
integral deadband (
Int deadband
) or Deadband and xx se cyclic (xx: 5 sec, 30 sec,
1 min). The reporting interval is controlled by the parameter
XDbRepInt
.
XDbRepInt
: This setting handles all the reporting types. If setting is deadband in
XRepTyp, XDbRepInt defines the deadband in m% of the measuring range. For
cyclic reporting type (
XRepTyp
:
cyclic
), the setting value reporting interval is in
seconds. Amplitude deadband is the setting value in m% of measuring range.
Integral deadband setting is the integral area, that is, measured value in m% of
measuring range multiplied by the time between two measured values.
XHiHiLim
: High-high limit. Set as % of
YBase
(Y is
SBase
for S,P,Q
UBase
for
Voltage measurement and
IBase
for current measurement).
1MRK 505 388-UEN B
Section 12
Monitoring
Busbar protection REB650 2.2 IEC
201
Application manual
Содержание REB650
Страница 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Страница 2: ......
Страница 18: ...12...
Страница 28: ...22...
Страница 38: ...32...
Страница 78: ...72...
Страница 96: ...90...
Страница 136: ...130...
Страница 150: ...144...
Страница 156: ...150...
Страница 232: ...226...
Страница 278: ...272...
Страница 298: ...292...
Страница 310: ...304...
Страница 320: ...314...
Страница 321: ...315...