margin from normal operation values. Phase voltages are not recommended for
trigging.
There is a risk of flash wear out if the disturbance report triggers
too often.
Remember that values of parameters set elsewhere are linked to the information on
a report. Such parameters are, for example, station and object identifiers, CT and
VT ratios.
12.7
Logical signal status report BINSTATREP
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
12.7.1
Identification
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical signal status report
BINSTATREP
-
-
12.7.2
Application
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v3
The Logical signal status report (BINSTATREP) function makes it possible to poll
signals from various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs
and can be read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the
input signal remains set for a longer period, the output will remain set until the
input signal resets.
t
t
INPUTn
OUTPUTn
IEC09000732-1-en.vsd
IEC09000732 V1 EN-US
Figure 73:
BINSTATREP logical diagram
1MRK 505 388-UEN B
Section 12
Monitoring
Busbar protection REB650 2.2 IEC
223
Application manual
Содержание REB650
Страница 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Страница 2: ......
Страница 18: ...12...
Страница 28: ...22...
Страница 38: ...32...
Страница 78: ...72...
Страница 96: ...90...
Страница 136: ...130...
Страница 150: ...144...
Страница 156: ...150...
Страница 232: ...226...
Страница 278: ...272...
Страница 298: ...292...
Страница 310: ...304...
Страница 320: ...314...
Страница 321: ...315...