background image

RARIC
Shaft current protection

1MRK 502 001-UEN

Page 9

The setting of the overcurrent relay RXIK 1 is suitably decided after
checking the magnitude of the stray current to the relay when the genera-
tor is running at load. In case of induced stray currents, a setting 50%
higher than the setting which gives unwanted operation is recommended.

The time delay set on time relay RXKL 1 should with margin override the
time delay of the phase short-circuit back-up impedance or overcurrent
protection. A normal setting is 3 s.

Set the overcurrent relay and the time relay according to the above. Insert
the RTXH 18 test handle into the RTXP 18 test switch.The primary oper-
ating current of the protection is tested by injecting current of rated fre-
quency into test winding A - B of the shaft current transformer from test
terminals 3B - 4B on the handle. The test winding has four turns, hence
the primary operate shaft current is four times the injected operate current.
Observe that for RARIC Version 2, rated frequency is 150 or 180 Hz. For
this version, the relay shall not operate at lowest setting when 3 V rated
frequency voltage is applied to relay terminals 107:231 - 241, (see Fig. 4).

Without altering the settings, interchange the leads to the test terminals
and check the operate value. It can be different from the earlier measured
value. Both values should be recorded for comparison at future tests.

Set the injection current to 2 times the operate value and check the time
delay.

Connect a brush via a test lead to an ammeter and then further to ground
via a series connected adjustable resistor, 0 - 30 ohms. When the machine
is running, press the brush against the shaft near the insulated bearing and
reduce the resistance until the relay operates. Record the operate current.

Check the external connections for the trip and alarm signals.

Under normal conditions RARIC requires no special maintenance.
The covers should be installed in place and the hole for the current setting
knob should be blanked off with a plastic plug.

Maintenance testing at regular intervals, say every second years, should be
made. The testing is suitably made by injection of current to the test wind-
ing, since this also checks the ILDD transformer and the wiring up to the
protection.

5 SETTING, TESTING AND COMMISSIONING

5.1 Setting

5.2 Testing and commissioning

5.2.1 Injection test

5.2.2 Primary test

6 MAINTENANCE

Содержание RARIC

Страница 1: ...the shaft Fundamental or third harmonic operating principle AC or DC powered galvanically isolated Shaft current transformer with test winding Can be applied to shafts with diameters up to 2960 mm Settable time delay Trip relay with heavy duty contacts and indicating flag Test switch Features User s guide 1MRK 502 001 UEN Revision A Issued January 2003 Data subject to change without notice ...

Страница 2: ...current transformer 5 3 MODE OF OPERATION 6 4 RECEIVING STORAGE AND INSTALLATION 8 4 1 Receiving 8 4 2 Storage 8 4 3 Installation 8 5 SETTING TESTING AND COMMISSIONING 9 5 1 Setting 9 5 2 Testing and commissioning 9 5 2 1 Injection test 9 5 2 2 Primary test 9 6 MAINTENANCE 9 7 TECHNICAL DATA 10 8 DIAGRAMS 12 9 DIMENSION ILDD 15 10 MOUNTING 16 ...

Страница 3: ...bearing and the ground structure a breakdown of the oil film insulation may give rise to a heavy current which leads to destruction of the bearing Consequently the bearing pedestal furthest from the prime mover is usu ally insulated from ground and the insulation should be supervised by a suitable protection Severe damage on the bearings is not expected to occur if the shaft current is less than o...

Страница 4: ... 4 only for RARIC Version 2 contains capacitors reactors and resistors One parallel resonance and one series resonance circuit in the filter gives the frequency char acteristic shown in Fig 4 3 Overcurrent relay RXIK1 is the measuring unit of RARIC The operating value of RXIK 1 is steplessly settable 0 5 2 mA The current input circuit has an resist ance of 82 ohms and contains an RC circuit to sup...

Страница 5: ...s split up in two parts for sizes with inner diameter up to and including 2 000 mm For larger diameters the transformer is split up in four parts When the parts are jointed the steel sheets of the core are interleaved with an overlap of about 30 mm The measuring winding with 400 800 turns depending on the diameter of the transformer is evenly distributed on the parts of the core When the transform...

Страница 6: ...e oil film in the bearing pulses are fed to RXIK 1 If these pulses exceed the operating value of the relay and the intervals between the pulses are shorter than 0 9 s the contacts of the out put relay will be continuously closed The impedance of the current measuring circuit in RXIK 1 is about 80 ohms Hence for Version 1 the operate voltage is about 40 mV at the low est setting 0 5 mA of RXIK 1 Fi...

Страница 7: ...g 0 5 resp 1 mA as func tion of the inner diameter of ILDD The filter in Version 2 rejects the fundamental voltage by more than 70 1 Fig 4 Operate voltage of RARIC Version 2 as function of frequency Rated frequency 50 Hz 502001 1 7 6 1 0 5 0 1 0 04 V 30 50 100 150 500 I 1 mA s I 0 5 mA s f Hz 502001 2 ...

Страница 8: ... the bearing is flowing in the shaft This means that it should be mounted at the rotor side of any bearing or slip ring To avoid disturbances the transformer shall be mounted on the turbine side of the machine which is free from field bars and at maximum distance from the end of the stator winding See Fig 12 and Fig 13 for recommended mounting Screened cable with twisted pairs and with the screen ...

Страница 9: ...hen 3 V rated frequency voltage is applied to relay terminals 107 231 241 see Fig 4 Without altering the settings interchange the leads to the test terminals and check the operate value It can be different from the earlier measured value Both values should be recorded for comparison at future tests Set the injection current to 2 times the operate value and check the time delay Connect a brush via ...

Страница 10: ...m aux voltage AC supply DC supply Approx 2 VA before and 8 VA after operation Approx 3 W before and 7 W after operation Time setting range RXKL 30 ms 99 h Permissible ambient temperature 5 to 55 C Permissible range auxiliary voltage supply 80 110 of rated voltage Table 2 Electromagnetic compability tests Power frequency test SS 436 15 03 0 5 kV class PL4 Fast transient test SS 436 15 03 4 8 kV cla...

Страница 11: ... for 1 s 5 4 A continuously Making and conducting capacity L R 10 ms 30 20 A for 200 ms 10 10 A for 1 s Breaking capacity dc L R 40 ms 2 1 5 A at 24 V 1 0 5 A at 48 V 0 4 0 2 A at 110 V 0 2 0 1 A at 220 V 7DEOH Weights and dimensions Weight RARIC version 1 RARIC version 2 ILDD 4 kg 5 kg 10 80 D 300 2300 kg where D is the inner diameter in mm Dimension RARIC version 1 RARIC version 2 ILDD 4U 24C 4U...

Страница 12: ...C converter RXTUG 22H 8 DIAGRAMS 7429010 AD 31 18 22 I 28 41 21 4B 4A 16A 16B 1A 1B 18A 18B I U 126 127 128 118 116 117 11B 11A 10B 10A 9B 9A 12B 12A 313 21 11 24 250V I I 1 2 101 107 113 119 313 RTXP 18 RXTUG 22H RXIK 1 RXKL 1 RXME 18 1 TRIPPING OF CB S ETC 2 ALARM ETC 24C 4S 3 3 LOSS OF EL 17A 17B 17 27 101 16 26 316 318 317 25 27 26 16 14 15 15 17 13 11 12 16 119 21 11 107 101 2A 2B 113 3B 3A 1...

Страница 13: ... Ver sion 2 with AC DC converter RXTUB 2 Fig 8 Terminal diagram 7429 010 ADA for RARIC RK 649 101 AD Version 1 7429010 FC S1 S2 A B I TRIPPING ETC ALARM ETC 220V 110V SHAFT CURRENT PROTECTION 100V 0V RARIC 16A 113 25 101 1A 18A 3B 101 4B 4A 3A 101 107 16 2A 319 26 17A 107 31 107 41 101 12A 11A 10A 9A 7429 010 ADA ...

Страница 14: ... I TRIPPING ETC ALARM ETC LOSS OF EL 24 250V SHAFT CURRENT PROTECTION RARIC 16A 119 25 107 316 107 318 107 317 101 1A 18A 107 116 107 118 3B 101 4B 4A 3A 101 113 16 2A 313 26 17A 113 31 113 41 101 U 7429 010 BAA S1 S2 A B TRIPPING ETC ALARM ETC 220V 110V 100V 0V RARIC 16A 125 25 101 1A 18A 3B 101 4B 4A 3A 101 119 16 2A 331 26 17A 107 231 107 241 101 12A 11A 10A 9A I 7429 010 FCA I SHAFT CURRENT PR...

Страница 15: ...halves are interconnected via the termi nals S All dimensions are in mm Transformer with D 2000 mm has the cross section dimensions accord ing to Alt 1 Transformer with D 2000 mm is split up in four parts and has the cross section according to Alt 2 9 DIMENSION ILDD Max 70 38 50 Alt 1 42 65 Max 85 Alt 2 D 5 AQ Trafo AB B A S2 S1 S en02000669 vsd S ...

Страница 16: ...dro generators Fig 13 Recommended mounting of the shaft current transformer ILDD on turbo generators 10 MOUNTING RARIC Oil film Bearing housing Insulation Rotor Turbine Shaft current transformer ILDD en03000001 vsd RARIC Generator Turbine Earthing Shaft current transformer ILDD Insulation Bearing Oil film Bearing en03000002 vsd ...

Страница 17: ...ld be mounted with 4 supports One of the alterna tives 1 2 or 3 can normally be used Except the supporting bar all details are the same for all alternatives Site weldings indicated for alternative 1 applies to all alternatives Fig 14 Examples of mounting supports en03000004 tif ...

Отзывы: