5 - Installation
P
VS-60-TL-US - PV input connection
- Confirm that PV array equipment ground wire(s) is connected to the
equipment ground connection point
16
(labelled “EGC”).
- Confirm the DC cables are
4AWG - 3/0AWG, copper or aluminum.
- Connect PV array to the the DC input terminal block
39
(+ and -).
- Torque screws to 14 N-m (10.3 ft-lb).
- When finished, go back and confirm the polarity is correct for each
string.
- Give each wire a pull test to confirm the connection is secure.
-Conduit must be attached using liquid tight fittings to maintain Type 4
enclosure integrity.