5 - Installation
I
nstallation procedure for quick-fit connectors
The model of connectors installed on your inverter must be matched by
the same model of the respective corresponding parts to be used (check
the corresponding part on the manufacturer's website or with ABB).
Using mating parts that are not compliant with the quick fit connector models on the inverter
could cause serious damage to the unit and lead to invalidation of the warranty.
CAUTION: To avoid damage to the equipment, when crimping cables to the connectors, pay
particular attention to polarity.
Complete assembly instructions and specification of quick-fit connectors could be find on ma-
nufacturer website.
Input cables must meet the connector requirements (cable diameter,
conductor cross section) and depends from connector models as shown
in the table below:
Type Manufacturer
Model
P/N
Conductor cross section Ø cable gland
Male
Stäubli
PV-KBT4-EVO 2
32.0087P0001-UR
32.0089P0001-UR
32.0093P0001-UR
4 - 6 mm²
4 - 6 mm²
10 mm²
4.7 - 6.4 mm
6.4 - 8.4 mm
6.4 - 8.4 mm
Female
Stäubli
PV-KST4-EVO 2
32.0086P0001-UR
32.0088P0001-UR
32.0092P0001-UR
4 - 6 mm²
4 - 6 mm²
10 mm²
4.7 - 6.4 mm
6.4 - 8.4 mm
6.4 - 8.4 mm
- Strip the cable over a lenght of 6,0 to 7,5mm using suitable equipment.
- Crimp the terminal to the conductor using the designated pliers.
6.0...7.5mm
*4...10mm
*4.7...8.4mm
(*): depending on connector models