Parameter
number
Description
Setting range
Number of
decimal
Fieldbus
ID
Default value Actual
setting
08
Sequence start
08.37
Kick start time seq 2
0.20 ... 2.00 s
2
0
0.20 s
08.38
Torque limit lvl seq 2
20 ... 200 %
0
0
150 %
08.39
Torque tune seq 2
0 ... 1000 %
0
0
100 %
08.40
Torque ctrl gain seq 2
0.01 ... 10.00
2
0
0.02
08.60
Ie seq 3
9.0 ... 1250 A
1
0
9.0 A
08.61
Start mode seq 3
Voltage ramp, Torque ramp, Full voltage start
0
0
Voltage ramp
08.62
Start ramp time seq 3
1 ... 120 s
0
0
10 s
08.63
Start ramp init lvl seq 3
10 ... 99 %
0
0
30 %
08.64
Curr lim level seq 3
0.5 ... 7.5 x
Ie
1
0
7.0 x
Ie
08.65
Kick start seq 3
On / Off
0
0
Off
08.66
Kick start level seq 3
50 ... 100 %
0
0
70 %
08.67
Kick start time seq 3
0.2 ... 2.00 s
2
0
0.2 s
08.68
Torque limit lvl seq 3
20 ... 200 %
0
0
150 %
08.69
Torque tune seq 3
0 ... 1000 %
0
-
100 %
08.70
Torque ctrl gain seq 3
0.01 ... 10.0
2
-
0.02
09
Automatic restart
09.01
Auto-reset delay time
0 ... 3600 s
0
-
0 s
09.02
Auto-restart
On / Off
0
-
Off
09.03
Auto-restart max attempts
1 ... 10
0
-
5
10
Internal IO
10.01
In0 function
None, Reset, Enable, Slow speed forward,
Slow speed reverse, Motor heating, Stand still
brake, Start reverse, User defined protection,
Emergency mode, Fieldbus disable control,
Start 1, Start 2, Start 3. *
0
130
Reset
10.02
In1 function
0 ... 15 *
0
131
None
10.03
In2 function
0 ... 15 *
0
132
None
10.04
K4 function
None, Run, Top of ramp, Event group 0, Event
group 1, Event group 2, Event group 3, Event
group 4, Event group 5, Event group 6,
Sequence 1 RUN, Sequence 2 RUN,
Sequence 3 RUN, Sequence 1 TOR, Sequence
2 TOR, Sequence 3 TOR,
Run reverse **
0
133
Run
10.05
K5 function
0 ... 17 **
0
134
Top of ramp
10.06
K6 function
None, Run, Top of ramp, Event group 0,
Event group 1, Event group 2, Event group 3,
Event group 4, Event group 5, Event group 6,
Sequence 1 Run, Sequence 2 Run,
Sequence 3 Run
0
135
Event group 0
10.07
AO reference
0-10 mA, 0-20 mA, 4-20 mA, 0-10 V
0
137
4-20 mA
10.08
AO type
Motor current [A], Mains voltage [V], Active
power [kW], Active power [HP], Reactive power
[kVAr], Apparent power [kVA], Active energy
[kWh], Reactive energy [kVArh], COS [
COS [Φ
],
Motor temperature [%], Thyristor temperature
[%], Motor voltage [%]
Mains frequency [Hz], PT100 temperature
[centigrade], PTC resistance [Ω]
0
138
Motor current
[A]
10.09
AO max value
0.0 ... 1000000.0
0
139
500.0
10.10
AO min value
0.0 ... 1000000.0
0
140
0.0
10.11
Ext therm sensor - ID
No sensor, PTC element, Three-wire PT100,
Two-wire PT100, Thermistor switch
0
-
No sensor
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание PSTX30
Страница 4: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 6: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 10: ...1 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 16: ...2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 26: ...3 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 32: ...4 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 44: ...5 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 64: ...6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 124: ...7 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 128: ...8 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 131: ...9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 132: ...9 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 142: ...10 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...
Страница 145: ...11 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...