7:1.1 Overview of all accessible settings (different menus) cont.
Description
Display
text
Setting
range
Default
value
Actual
setting
Function of programmable input In1
In1
None, Reset,
Enable Jog, DOL,
Start 3, FB-Dis
Reset
Function of programmable output relay K4
Relay K4
Run, TOR, Event
Run
Function of programmable output relay K5
Relay K5
Run, TOR, Event
TOR
Function of programmable output relay K6
Relay K6
Run, TOR, Event
Event
Function of programmable software relay V7
SW Outp V7
Run, TOR, Event
Event
Overload event of relay K4
K4 Overload
Yes, No
No
Fault event of relay K4
K4 Fault
Yes, No
No
Shunt fault of relay K4
K4 Shunt Fault
Yes, No
No
High current event of relay K4
K4 High I
Yes, No
No
Thyristor overload event of relay K4
K4 SCR OL
Yes, No
No
Locked rotor event of relay K4
K4 Lock Rot
Yes, No
No
Underload event of relay K4
K4 Underload
Yes, No
No
Phase imbalance event of relay K4
K4 Phase Imb
Yes, No
No
PTC event of relay K4
K4 PTC
Yes, No
No
Phase reversal event of relay K4
K4 Phase Rev
Yes, No
No
Warning motor overload event of relay K4
K4 Warn OL
Yes, No
No
Warning thyristor overload event of relay K4
K4 Wa SCR OL
Yes, No
No
Warning high current event of relay K4
K4 Wa I=High
Yes, No
No
Warning low current event of relay K4
K4 Wa I=Low
Yes, No
No
Overload event of relay K5
K5 Overload
Yes, No
No
Fault event of relay K5
K5 Fault
Yes, No
No
Shunt fault of relay K5
K5 Shunt Fault
Yes, No
No
High current event of relay K5
K5 High I
Yes, No
No
Thyristor overload event of relay K5
K5 SCR OL
Yes, No
No
Locked rotor event of relay K5
K5 Lock Rot
Yes, No
No
Underload event of relay K5
K5 Underload
Yes, No
No
Phase imbalance event of relay K5
K5 Phase Imb
Yes, No
No
PTC event of relay K5
K5 PTC
Yes, No
No
Phase reversal event of relay K5
K5 Phase Rev
Yes, No
No
Warning motor overload event of relay K5
K5 Warn OL
Yes, No
No
Warning thyristor overload event of relay K5
K5 Wa SCR OL
Yes, No
No
Warning high current event of relay K5
K5 Wa I=High
Yes, No
No
Warning low current event of relay K5
K5 Wa I=Low
Yes, No
No
Overload event of relay K6
K6 Overload
Yes, No
Yes
Fault event of relay K6
K6 Fault
Yes, No
Yes
Shunt fault of relay K6
K6 Shunt Fault
Yes, No
Yes
High current event of relay K6
K6 High I
Yes, No
Yes
Thyristor overload event of relay K6
K6 SCR OL
Yes, No
No
Locked rotor event of relay K6
K6 Lock Rot
Yes, No
No
Underload event of relay K6
K6 Underload
Yes, No
No
Phase imbalance event of relay K6
K6 Phase Imb
Yes, No
No
PTC event of relay K6
K6 PTC
Yes, No
No
Phase reversal event of relay K6
K6 Phase Rev
Yes, No
No
Warning motor overload event of relay K6
K6 Warn OL
Yes, No
No
Warning thyristor overload event of relay K6
K6 Wa SCR OL
Yes, No
No
Warning high current event of relay K6
K6 Wa I=High
Yes, No
No
Warning low current event of relay K6
K6 Wa I=Low
Yes, No
No
Overload event of relay V7
V7 Overload
Yes, No
Yes
Fault event of relay V7
V7 Fault
Yes, No
Yes
High current event of relay V7
V7 High I
Yes, No
Yes
Thyristor overload event of relay V7
V7 SCR OL
Yes, No
No
Locked rotor event of relay V7
V7 Lock Rot
Yes, No
No
Underload event of relay v7
V7 Underload
Yes, No
No
Phase imbalance event of relay V7
V7 Phase Imb
Yes, No
No
Chapter 7
Settings and configuration
7.6
Low Voltage Products & Systems
1SXU 132 021 M0201
ABB nc. • 888-385-1221 • www.abb-control.com