10:72 Month
Path in menu:
Menu/SETTINGS/Presentation Set./Date Month
This parameter makes it possible to set the current month for the real time clock.
Parameter text
Default value
Setting range
Description
Date Month
Individual
1...12
Month
10:73 Day
Path in menu:
Menu/SETTINGS/Presentation Set.Date Day
This parameter makes it possible to set the current day for the real time clock.
Parameter text
Default value
Setting range
Description
Date Day
Individual
1...31
Day
10:74 Hour
Path in menu:
Menu/SETTINGS/Presentation Set./Time Hour
This parameter makes it possible to set the current hour for the real time clock.
Parameter text
Default value
Setting range
Description
Time Hour
Individual
0...23
Hour
10:75 Minutes
Path in menu:
Menu/SETTINGS/Presentation Set./Time Min
This parameter makes it possible to set the current minutes for the real time clock.
Parameter text
Default value
Setting range
Description
Time Min
Individual
0...59
Minutes
10:76 By-pass doesn’t open, type of operation (BP Closed Op)
Path in menu:
Menu/SETTINGS/Functional Settings/Faults/BP Closed Op
This parameter makes it possible to select between two different actions of the softstarter if
the by-pass contactor does not open in a proper way.
Stop-M The motor stops and a manual reset is required before restart.
Stop-A
The motor stops and an automatic reset is performed when the fault disappears
Parameter text
Default value
Setting range
Description
BP Closed Op
Stop-M
Stop-M, Stop-A
Type of operation if the
bypass does not open
10:77 By-pass doesn’t close, type of operation (BP Open Op)
Path in menu:
Menu/SETTINGS/Functional Settings/Faults/BP Open Op
This parameter makes it possible to select between two different actions of the softstarter if
the by-pass contactor does not close in a proper way.
Stop-M The motor stops and a manual reset is required before restart.
Stop-A
The motor stops and an automatic reset is performed when the fault disappears
Parameter text
Default value
Setting range
Description
BP Open Op
Stop-M
Stop-M, Stop-A
Type of operation if the
bypass does not close
Chapter 10
Functions
Low Voltage Products & Systems
10.19
ABB Inc. • 888-385-1221 • www.abb-control.com
1SXU 132 021 M0201
10