![ABB PST30 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/abb/pst30/pst30_installation-and-maintenance-manual_3390451014.webp)
3:8 Technical data
3:8.1 General
Item
Technical data
Rated insulation voltage, Ui
690V
Rated operational voltage, Ue
208-690 V (in two modes)
Rated control voltage, Us
100 - 250 V 50/60 Hz
Rated frequency
50 / 60 Hz
Voltage tolerances
+10% to -15%
Frequency tolerances
±5%
Rated impulse withstand voltage
2 kV
Number of controlled phases
3
Programmable inputs
24 VDC, 10 mA
Output relays
250 VAC, Ith = 5A, le = 1.5A (AC-15)
Battery back-up D20mm
Lithium 3V CR2032
PTC input
2825 ohm ±20% switch off resistance
1200 ohm ±20% switch on resistance
Cooling system
Fan
Recommended fuse for control circuit
6A Delayed
MCB use C characteristics
Service factor
115% (100% for PSTB1050)
Communication protocols
AS-Interface DeviceNet / Profibus DP /
Modbus
Chapter 3 - Description
3:8.2 Semi-conductor fuses
Softstarter type
Bussmann fuses
Holders
A
Type
PST30
80
170M1366
170H1007
PST37
125
170M1368
170H1007
PST44
160
170M1369
170H1007
PST50
160
170M1369
170H1007
PST60
200
170M1370
170H1007
PST72
250
170M1371
170H1007
PST85
315
170M1372
170H1007
PST105
400
170M3019
170H3004
PST142
450
170M3020
170H3004
PST175
500
170M3021
170H3004
PST210
630
170M5012
170H3004
PST250
700
170M5013
170H3004
PST300
900
170M5015
170H3004
PSTB370