Chapter 10
Functions
10:43 Phase loss fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/Ph Loss Op
This parameter makes it possible to select between two different actions if a phase loss fault
occurs.
Stop-M The motor stops and a manual reset is required before restart
Stop-A The motor stops and an automatic reset is performed when the fault
disappears
Parameter text
Default value
Setting range
Description
Ph Loss Op
Stop-M
Stop-M, Stop-A
Type of operation for
phase loss fault
10:44 Fieldbus fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/FB Fault Op
This parameter makes it possible to select between two different actions if a fault occurs in
the fieldbus communication.
Stop-M The motor stops and a manual reset is required before restart
Stop-A The motor stops and an automatic reset is performed when the fault
disappears
Parameter text
Default value
Setting range
Description
FB Fault Op
Stop-M
Stop-M, Stop-A
Type of operation for
fieldbus fault
10:45 Frequency fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/Freq F Op
This parameter makes it possible to select between two different actions if the frequency is
out of range (frequency fault).
Stop-M The motor stops and a manual reset is required before restart
Stop-A The motor stops and an automatic reset is performed when the fault
disappears
Parameter text
Default value
Setting range
Description
Freq F Op
Stop-M
Stop-M, Stop-A
Type of operation for
frequency fault
10:46 Heatsink over-temperature fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/HS Temp Op
This parameter makes it possible to select between two different actions if the heat sink
temperature of the softstarter is too high.
Stop-M The motor stops and a manual reset is required before restart
Stop-A The motor stops and an automatic reset is performed when the fault
disappears
Parameter text
Default value
Setting range
Description
HS Temp Op
Stop-M
Stop-M, Stop-A
Type of operation for
heat sink overtempera-
ture fault
10.12
Low Voltage Products & Systems
1SXU 132 021 M0201
ABB Inc. • 888-385-1221 • www.abb-control.com
10