Transport – storage – unpacking
3.1
Visual inspection
Upon receiving the goods, make sure that they corresponds to the material indicated in the delivery
note. Carefully examine the packed unit(s) for any sign of physical damage. Two TiltWatch indicators
(see Figure 2) are placed on two sides of the packed unit, in a well visible position. They should both be
intact and not red color. If tipping has occurred the white arrow becomes red, like shown on the Figure
2 below.
In case of damaged unit(s) or even only suspect of damaged (TiltWatch is red) inform immediately:
•
The carrier
•
The manufacturer
IMPORTANT
NOTES!
VISIBLE TRANSPORT DAMAGES MUST BE CLAIMED TO THE CARRIER
IMMEDIATELY AFTER RECEIPT.
OTHER CLAIM FOR SHIPPING DAMAGE MUST BE FILED ALSO
IMMEDIATELY AND THE CARRIER MUST BE INFORMED WITHIN 7 DAYS
OF RECEIPT OF THE EQUIPMENT. THE PACKING MATERIALS SHOULD
BE STORED FOR FURTHER INVESTIGATION.
Figure 2: TiltWatch indicator: left when intact and right when tipping has occurred.
3.2
Storage
The packing of the goods protects it from mechanical and environmental damage. UPS and Battery
cabinets should be store in its original packaging. Make sure that the goods are stored indoor, protected
from water and sunshine in a clean environment.
IMPORTANT
NOTES!
THE RECOMMENDED TEMPERATURE FOR STORAGE OF THE UPS
SYSTEM AND BATTERIES IS B20 °C AND +25°C, HUMIDITY <
95% (NON-CONDENSING).
FOR UPS SYSTEM ONLY THE STOREAGE TEMPERATURE CAN BE
BETWEEN -25 °C AND +70°C, HUMIDITY < 95% (NON-CONDENSING).
BEFORE SWITSIHG ON THE UNIT(S), MAKE SURE THE AMBIENT
TEMPERATURE HAS REACHED THE OPERATION TEMPERATURE RANGE
WHICH IS 0°C - +40°C.