Navigator 600 Phosphate
Multi-stream
13 Specification
IM/NAV6P/MS–EN Rev. F
61
13 Specification
Phosphate Measurement
Range
Fully user programmable 0 to 15 ppm PO
4
(0 to 5 ppm P),
minimum range 0 to 1 ppm PO
4
(0 to 0.33 ppm P)
Measurement Modes
Continuous
Continuous measurement operation
Sample stream options
Available in 1, 2, 4 or 6 streams (4 and 6 stream configurations can
accommodate 3 and 5 streams respectively, if required)
Measurement Performance
Response time
<15 mins. (90 % step change)
Typical accuracy
<±3 % of reading or ±0.1 ppm (whichever is the greater) over the
range 0 to 10 ppm PO
4
<±5 % of reading over the range 10 to 15 ppm PO
4
Repeatability
<±1.5 % of reading or ±0.05 ppm (whichever is the greater) over the
range 0 to 10 ppm PO
4
<±2.5 % of reading over the range 10 to 15 ppm PO
4
Range
Auto ranging 0.00 to 2.99 /3.0 to 15.0
Solution Requirements
Number
2 reagents
2 standard solution
1 cleaning solution
Volume
2.5 l max. per reagent
500 ml per standard solution
500 ml cleaning solution
Reagent Consumption
Continuous operation mode
2.5 l max. per 90 days
Display
Color, passive matrix, liquid crystal display (LCD) with built-in
backlight and contrast adjustment
76800 pixel display*
*A small percentage of the display pixels may be either constantly
active or inactive. Max. percentage of inoperative pixels <0.01%.
Dedicated operator keys
Group Select/Left cursor
View Select/Right cursor
Menu key
Up/Increment key
Down/Decrement key
Enter key
Mechanical Data
Ingress protection
Dimensions
Materials of construction
**Not evaluated for UL or CB
Diagonal display area
144 mm (5.7 in.)
IP31** – Wet section (critical components IP66)
IP66 –
Transmitter
Height
638 mm (25.1 in.) plus constant head
bracket 186 mm (7.3 in.)
Width
271 mm (10.7 in.)
Depth
182 mm (7.2 in.)
Weight
15 kg (33 lbs)
Electronics enclosure
20 % glass loaded polypropylene
Main enclosure
Noryl
Lower tray
10 % glass loaded polypropylene
Door
Acrylic