![ABB MTAC-01 Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/abb/mtac-01/mtac-01_user-manual_2749023.webp)
23
Diagnostics
Diagnostics
Faults/Alarms
If the ACS350 detects that the encoder signal is lost, the drive
operation and the diagnostic message are both controlled by
parameter
5003
ENCODER FAULT:
•
5003
= 1 (FAULT) – The drive generates a fault
(23 ENCODER ERR), and the motor coasts to a stop.
•
5003
= 2 (ALARM) – The drive generates an alarm
(2024 ENCODER ERROR) and operates as if parameter
5002
ENCODER ENABLE = 0 (DISABLE), that is, speed
feedback is derived from the internal motor model.
In case of a fault or alarm signal, check for and correct the
following:
Note:
The validity of the encoder signal is also checked during the
ID run. See parameter 9910 MOTOR ID RUN. If the drive detects
an encoder problem during the ID run, the drive generates an
alarm. Parameter 5003 ENCODER FAULT controls the drive’s
fault/alarm response to encoder errors only after the ID run is
completed.
CODE FAULT/ALARM
1)
CAUSE
WHAT TO DO
0023
ENCODER ERR
(7301)
0306 bit 6
Communication fault
between pulse encoder
and pulse encoder
interface module or
between module and
drive.
Check pulse encoder and its
wiring, pulse encoder
interface module and its
wiring and parameter group
50 ENCODER
settings.
2024
ENCODER ERROR
(7310)
0309 bit 7
1)
Name, code for fieldbus communication (in parentheses) and bit in fault/alarm word.