![ABB MTAC-01 Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/abb/mtac-01/mtac-01_user-manual_2749012.webp)
12
Installation
Wiring – General
The pulse encoder should be connected to the MTAC-01 module
with cables as specified below.
Terminal designations
Use the following table for reference when wiring terminals.
Cable construction
4 × (2+1) twisted pair cable with
individual and overall shields
Conductor cross-sectional area
0.5 to 1.5 mm
2
20 to 16 AWG
Maximum cable length
100 m
330 ft
Identification
Description
MTAC Encoder
SCR
SCR/
Shield
Used for grounding of the encoder cable shields.
Connected internally to the drive ground.
SCR
V
in
V
cc
/PWR Connected to the external power supply.
V
out
V
cc
/PWR Connected to the encoder.
GND 0 V / GND One connected to the ground of the external power
supply and the other to the ground of the encoder.
GND
A
1
A A+ • Max. signal frequency: 200 kHz
• Signal levels:
• Decision levels are automatically defined based
on the daisy chained power supply voltage level.
• Input channels are isolated from the logic and
ground.
• When the drive runs in the
Forward
direction,
channel A should lead channel B by 90°
(electrical).
• Channel Z: One pulse per revolution (used in
positioning applications only).
A
1
A A-
B
2
B B+
B
2
B B-
Z
3
Z Z+
Z
3
Z Z-
Logic “1”
Logic “0”
24 V
12.1 V
8.3 V
15 V
7.5 V
5.3 V
5 V
2.5 V
1.9 V
Содержание MTAC-01
Страница 1: ...ABB Drives User s Manual Pulse Encoder Interface Module MTAC 01 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...6 Safety ...
Страница 8: ...8 Table of contents ...
Страница 26: ...26 Technical data ...
Страница 27: ......