![ABB MTAC-01 Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/abb/mtac-01/mtac-01_user-manual_2749016.webp)
16
Installation
Wiring diagrams
Push-pull type encoder output
Diagram assumes normal pulse order in Forward
rotation: Pulse A/1 leads as diagrammed on the
right.
For encoders with pulse 2 leading, change the diagram for these
connections:
• Encoder A/1 and B/2 should be wired to MTAC terminals B and A,
respectively.
• Encoder A/1 and B/2 (if present) should be wired to MTAC terminals
B and A, respectively.
Differential connection
A/1
B/2
1
1
0
0V V
CC
2
2
0
SCR
1)
A
A
B
B
Z
Z
MTAC-01 module
1) Connect the cable shield at the encoder housing, if, and only if, the encoder is
isolated from the motor, and from the ground.
Encoder
power
supply
SCR
V
in
GND
V
out
GND
SCR
Encoder