I N S TA L L AT I O N , O P ER AT I O N S A N D M A I N T EN A N C E M A N UA L
Wrapping incoming power cables
Securely lace and support the incoming cables as
the following steps.
Wrap conductors using 1/2 in. (12.7 mm) diameter
sisal rope or equivalent. Wrap conductors on 9 in.
(227 mm) from the point where power conductors
leave the enclosure at least four times and pull the
rope tout.
Wrap the rope several times to fill the space
between the cables and pull the rope tout.
Repeat the last action between the other cables, tie
both rope ends between them, cut excess rope and
tape the ends.
Wiring between shipping splits
Run interconnecting wiring between sections in
a shipping split through the horizontal wireway
in the top and bottom of each section. To make
connections between shipping splits, a pull-apart
terminal block usually will be provided.
• Locate and uncoil removable shipping split
terminals, refer to MCC connection drawings
provided in the Quality Dossier.
• Once the wiring is uncoiled, locate the terminals
according to the number marked on them.
• Connect the removable terminal block to the
fixed terminal block according to the marked
numbering.
• To make the communication connection, refer
to connection drawings in the communication
section and locate the plug in connectors in the
shipping section.
• Connect the male and female communication
connectors following their guide.
—
55
—
56
—
57
—
58
—
55 Wrap power cables
—
56 Fill the space
between conductors
—
57 Finish wrapping
conductors
—
58 Shipping split
terminal blocks
227 mm