I N S TA L L AT I O N , O P ER AT I O N S A N D M A I N T EN A N C E M A N UA L
Top horizontal wireway
The MNS-MCC has a 277.5 mm (10.9 in) top
horizontal wireway.
The top horizontal wireway provides the space for
interconnection wiring. It is covered by a steel,
hinged door secured by a quarter- turn latch.
See Fig. 13 (Top Horizontal Wireway).
Bottom horizontal wireway
The bottom horizontal wireway is 175 mm (6.9 in)
high. The wireway contains the horizontal ground
bus, and is covered by a hinged door secured by a
quarter-turn latch. See Fig. 14 (Bottom Horizontal
Wireway).
Arc resistant features
The MNS-MCC Arc Resistant provides industry
leading features that afford operators the highest
degree of safety and efficiency while performing
both normal and maintenance operations.
• Motor control center designed to address the
causes of arc flash and other electrical safety
hazards such as shock and electrocution
• Tested to IEEE C37.20.7-2007 guide without
any current limiting main device
• Multifunction wall provides fault free zone with
finger-proof touch protection
• Bus shutters are not required
• MCC units are removed and replaced without
opening the door
• No tools required for unit removal
• Control wires and communication cables with
disconnecting terminal blocks do not require
manual disconnecting and reinstallation for unit
removal
• Once removed, unit maintenance or
modifications can be safely performed outside
of the arc flash boundary
An internal arcing fault can be a very rapid and
destructive event. Under the specified installation
conditions, an arc resistant enclosure withstands
the effects of the arc.
Testing was carried out on an array of samples of
varying construction, representing the worst case
installation scenarios. MNS-MCC provide type 2
accessibility (front, sides and rear) on systems
with available fault currents up to 65k A at 600V.
During evaluation testing, the maximum thermal
energy measured at the front of the gear was
below 1.2 cal/cm2.
—
14
—
13
—
13 Top horizontal wireway
—
14 Bottom horizontal
wireway