77/86
MegaFlex 1000 to 1600
UPS User Manual / REV-A
7.3.5
Restore to normal operation after “System shutdown” with Load not supplied
Warning!
Please check and ensure the conditions of the connected load are safe before proceeding, as this
procedure will result in the connection of power to the load circuit(s).
Note!
Before performing this operation, make sure that all units of the RPA Parallel System are in the
following status:
“Q1 – External UPS Output Circuit Breaker” must be closed (Pos. I).
“External Battery Breaker” must be open (Pos. O).
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting
this procedure.
View of the Synoptic Diagram, on all UPS units, after
performed the command “System shutdown” with load
not supplied.
1. Restore the command “System shutdown” of the RPA Parallel System.
Restore the command “System shutdown”, on anyone of the
parallel units, through
the screen:
Commands 1 / System shutdown /
RESET
.
•
The Load is supplied by the Utility through the Automatic Bypass of all Units.
•
Rectifiers start automatically, blinking LED 1 (Rectifier) indicates Soft-start.
•
At the end of Rectifier Soft-start, the LED 1 (Rectifier) remains lit.
•
LED ALARM are lit.
The Synoptic Diagram, on all UPS units, must display the status “
Load supplied by Automatic Bypass
”.
Synoptic diagram of first unit
Synoptic diagram of other units
Continue
→