68 OI/FEP610/FEH610-EN Rev. B |
ProcessMaster FEP610, HygienicMaster FEH610
8.3
Overview
Errors encountered are itemized in tabular form on the following pages. The response of the transmitter on error detection is
described therein. The table lists all possible errors together with a description of their impact on the value of measurement
variables, the properties of current outputs and the alarm output.
Error no. /
Range
Error text
Current output
Digital output
Pulse output
LCD display
Error maskable?
F099.042 /
Electronics
ADC overrange alarm.
Noise too high. Check
applicati. Call service.
High Alarm or Low
Alarm, depending
on parameter
"Curr.Out at
Alarm".
General Alarm, if
DO is configured
as "Logic / Alarm
Signal"
0 Hz
0 %
No
F098.012 /
Electronics
FEB communication error.
EMC disturbance. Call ABB
Service.
0 Hz
0 %
No
F097.029 /
Electronics
Coil regulation error.
Check wiring of sensor coils.
Call service
0 Hz
0 %
No
F096.043 /
Electronics
SIL self check alarm.
Call service.
Current value -
no change.
Current value -
no change.
No
F095.036 /
Electronics
Coil isolation alarm.
Call service.
Current value -
no change.
Current value -
no change.
No
F094.022 /
Electronics
Safety Alarm Curr. Out 31 /
32
SIL function detects error.
Call Service.
Current value -
no change.
Current value -
no change.
No
F093.032 /
Electronics
Electrode short cuircit.
Check wiring of sensor
electrode. Call service.
0 Hz
0 %
No
F092.033 /
Electronics
Electrode open cuircit.
Check wiring of sensor
electrode. Call service.
0 Hz
0 %
No
F091.030 /
Electronics
Coil wiring error.
Check wiring of sensor coils.
Call service.
0 Hz
0 %
No
F090.035 /
Electronics
ADC RX210 com. error.
Call service.
0 Hz
0 %
No
F088.013 /
Electronics
FEB communication error.
EMC disturbance. Call ABB
Service.
0 Hz
0 %
No
F086.019 /
Electronics
Curr.Out 31 / 32 com error.
Defective Board. EMC
disturbance. Call Service.
Current value -
no change.
Current value -
no change.
No
F084.011 /
Electronics
NV data defect.
Data storage irreparable.
Call Service.
0 Hz
0 %
No
F082.014 /
Electronics
Incompatible Frontend
Board.
Frontend not fit to
Motherboard. Call Service.
0 Hz
0 %
No
F081.026 /
Electronics
MB voltages outside range.
Defective Motherboard HW.
Call Service.
0 Hz
0 %
No