36 OI/FEP610/FEH610-EN Rev. B |
ProcessMaster FEP610, HygienicMaster FEH610
Easy Setup
Pulse Width
30.00 ms
Next
Edit
22. Use
to call up the edit mode.
23. Use
/
to set the desired pulse width.
24. Confirm the selection with
.
Easy Setup
Damping
30.00 ms
Next
Edit
25. Use
to call up the edit mode.
26. Use
/
to set the damping for the volume flow.
27. Confirm the selection with
.
Easy Setup
Dig.Out 41 / 42 Mode
Pulse
Next
Edit
28. Use
to call up the edit mode.
29. Use
/
to select the desired operating mode (Off,
Logic, Pulse, Frequency) for the digital output.
30. Confirm the selection with
.
Easy Setup
Curr.Out at Alarm
High Alarm
Next
Edit
31. Use
to call up the edit mode.
32. Use
/
to select the desired alarm mode.
33. Confirm the selection with
.
Easy Setup
Low Alarm
3.500 mA
Next
Edit
34. Use
to call up the edit mode.
35. Use
/
to set the alarm current for "Low Alarm".
36. Confirm the selection with
.
Easy Setup
High Alarm
21.800 mA
Next
Edit
37. Use
to call up the edit mode.
38. Use
/
to set the alarm current for "High Alarm".
39. Confirm the selection with
.
Zero point adjustment of the flowmeter
NOTE
Prior to starting the zero point adjustment, make sure that:
— There is no flow through the sensor (close valves, shut-
off devices etc.).
— The sensor is completely filled with the medium to be
measured
Easy Setup
System Zero
Next
OK
— Use
to start automatic balancing of the zero point for
the system.
Menu
Easy Setup
Exit
Select
Once all parameter have been set, the main menu appears
again. The most important parameters are now set.
40. Use
to switch to the process display.
Change from two to one column