6.4.5
Do a check on the electrical parts
Preliminary requirements
•
Only do this procedure
when another procedure
refers to it.
•
Procedure
1. Make sure that these parts on the AC plate are in the correct condition or
position. For the location of the electrical parts, refer to section
.
Part
Condition / Position
Fuse F10
it conducts power
Fuse F21
it conducts power
Fuse F22
it conducts power
Circuit breaker Q2
Off
6.4.6
Set the precommissioning switch
Preliminary requirements
•
Only do this procedure
when another procedure
refers to it.
•
Procedure
1. Make sure that these fuses are
serviceable:
•
F10
•
F21
•
F22
2. Set these circuit breakers to OFF:
•
Q1
•
Q2
3. Set the precommissioning switch Q10
to the position 0. For the location of
Q10, refer to
.
4. Energize the 120 V AC connection for
the precommissioning mode.
5. Measure the voltage before the breaker Q2. It must be 120 V AC.
6. Set the breaker Q2 to ON.
7. Set the precommissioning switch Q10 to the postion 1 (EXT).
0
1
2
EXT
INT