4. Connect these wires:
•
V+ wire (A) from the external customer interface, wire number 1, to the
terminal X1-1 (I)
•
V+ wire (B) from the secondary power cabinet, wire number 1, to the terminal
X1-2 (J)
•
V- wire (C) from the external customer interface, wire number 2, to the
terminal X1-3 (K)
•
V- wire (D) from the secondary power cabinet, wire number 2, to the terminal
X1-4 (L)
•
Rin wire (E) from the external customer interface, wire number 3, to the
terminal X1-5 (M)
•
Rin wire (F) from the secondary power cabinet, wire number 3, to the
terminal X1-6 (N)
•
Rout wire (G) from the external customer interface, wire number 4, to the
terminal X1-7 (O)
•
Rout wire (H) from the secondary power cabinet, wire number 4, to the
terminal X1-8 (P)
5. Tighten the screws to the correct torque. For the specification, refer to section
7.9
Connect the control cable for the tilt sensors to the
secondary power cabinet (option)
Preliminary requirements
•
Torque screwdriver, cross
•
Wire cutter
•
Wire stripper pliers
•
Crimp pliers
•
Control cable for the tilt
sensors. Refer to section
•
Ferrules
Procedure
1. Strip the insulation from the ends of
the wires (A) to (H). For the
specification, refer to section
.
2. Crimp ferrules onto the end of the
wires.
3. Loosen the screws of the terminal
block X-1.
F
G
H
E
B
C
D
A
I
J K L M N
P
O
Electrical installation of the power cabinet
9AKK107992A6488-EN | 004