Cable conduit
Maximum diameter
[mm]
[in]
Small holes in the foundation of the
charge post
60
2.36
Large holes in the foundation of the
charge post
125
4.92
12.19
Cable specifications
12.19.1
AC input cable for the power cabinet
Parameter
Specification
Cores
3 wires + PE, according to IEC 60446
Cross section range
185 mm² to 240 mm² (365 kcmil to 474
kcmil)
Conductor
Bare copper, fine wired, bunch stranded,
according to VDE 0295 Cl.5/IEC Cl.5
Diameter of the phase conductors
Refer to the local rules.
Insulation
PVC that is serviceable for outdoor use,
UV-protected, and oil resistant
Minimum nominal voltage Uo/U
450/750 VAC
Minimum test voltage
4 kV
Ambient temperature range
-40 °C to +80 °C (-40 °F to +176 °F)
Diameter of the PE conductor
The same as the diameter of the phase
conductors
12.19.2
DC power installation cables
The below data are specific for the DC power cables between the power cabinet and
the charge post.
Parameter
Specification
Type
1x Positive, 1x negative cable
Flexible
Unshielded
Number of cores
1
Cross section range (minimum)
185 mm² (365 kcmil)
Cross section range (maximum)
300 mm² (592 kcmil)
Diameter
27 to 35 mm (1.1 to 1.4 in)
Maximum length
60 m (197 ft)
Conductor
Fine wire, stranded in tin plated copper
or aluminum, according to VDE 0295
cl.5/IEC Cl.5
Diameter of the phase conductors
Refer to the local rules.
Insulation
Rubber or PVC that is serviceable for
outdoor use, UV-protected, and oil re-
sistant
Technical data
9AKK107992A6488-EN | 004
97
Содержание HP CP500
Страница 103: ...Technical data 9AKK107992A6488 EN 004 103 ...
Страница 104: ......