Function
Color
Name
Establishing communication to drive
Flashing green
HOST
Connection to drive OK
Green
Communication to drive lost temporarily
Flashing red
Internal file system error. The error may be cleared by cycling drive
power. If the error persists, contact your local ABB representative.
Flashing orange, al-
ternating with the
MODULE flashing
orange
There is no PC tool connected to the device.
Off
MODULE
Device is attempting to obtain IP configuration from the DHCP
server.
Flashing orange
Device is executing Duplicate Address Detection.
Orange
PC tool is connected to the device.
Green
Ethernet link is down.
Flashing red
Ethernet interface is disabled. Duplicate Address Detection may
have detected a duplicate address. Check the IP configuration and
either initiate a Fieldbus Adapter parameter refresh or cycle power
to the drive.
Red
Internal file system error. The error may be cleared by cycling drive
power. If the error persists, contact your local ABB representative.
Flashing orange, al-
ternating with the
HOST flashing or-
ange
Ethernet link is down.
Off
NETWORK /
NET
Ethernet link is up at 100 Mbps.
Flashing indicates activity on interface.
Flashing green
Ethernet link is up at 10 Mbps.
Flashing indicates activity on interface.
Flashing orange
68 NONE – Diagnostics
Содержание FMBT-21
Страница 1: ... OPTIONS FOR ABB DRIVES CONVERTERS AND INVERTERS FMBT 21 Modbus TCP adapter module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 16: ...16 ...
Страница 20: ...20 ...
Страница 46: ...46 ...
Страница 58: ...58 ...
Страница 66: ...66 ...
Страница 72: ...72 ...
Страница 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Страница 76: ...76 ...
Страница 80: ...80 ...
Страница 84: ...84 Appendix D FMBT 21 configuration web pages ...
Страница 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...