Register Data (16-bit)
Register Address
1) 2)
Native Drive Profile Actual 1 - Least Significant 16-bits
(4)00053
Native Drive Profile Actual 1 - Most Significant 16-bits
(4)00054
Native Drive Profile Actual 2 - Least Significant 16-bits
(4)00055
Native Drive Profile Actual 2 - Most Significant 16-bits
(4)00056
DATA IN 1
(4)00057
DATA IN 2
(4)00058
DATA IN 3
(4)00059
DATA IN 4
(4)00060
DATA IN 5
(4)00061
DATA IN 6
(4)00062
DATA IN 7
(4)00063
DATA IN 8
(4)00064
DATA IN 9
(4)00065
DATA IN 10
(4)00066
DATA IN 11
(4)00067
DATA IN 12
(4)00068
Drive Parameter Access (16-bit): Register Address = 100 × Group +
Index
(4)00101… (4)09999
Example for Drive Parameter 3.18: (4)00000 + 100 × 3 + 18 = 400318
Note: Addressing depends on the address mode selected with parameter
group 23 in group A (51/151, 54/154).
Drive Parameter Access (32-bit): Register Address = (4)20000 + 200 × Group
+ 2 × Index
(4)20000… (4)29999
Example for Drive Parameter 1.27: (4)20000 + 200 × 1 + 2 × 27= 420254
Note: Addressing depends on the address mode selected with parameter
group 23 in group A (51/151, 54/154).
1) 6-digit register addressing ([4]00001) is used instead of 5-digit register addressing ([4]0001) to describe the
register map. See section
for additional information.
2) Register addresses of the 32-bit parameters cannot be accessed by using 5-digit register numbers.
54 Modbus/TCP – Communication protocol
Содержание FMBT-21
Страница 1: ... OPTIONS FOR ABB DRIVES CONVERTERS AND INVERTERS FMBT 21 Modbus TCP adapter module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 16: ...16 ...
Страница 20: ...20 ...
Страница 46: ...46 ...
Страница 58: ...58 ...
Страница 66: ...66 ...
Страница 72: ...72 ...
Страница 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Страница 76: ...76 ...
Страница 80: ...80 ...
Страница 84: ...84 Appendix D FMBT 21 configuration web pages ...
Страница 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...