1SDH000510R0001
25/28
Page N.
L2388
EP010
ABB SACE
184 Prot I threshold
{1,5 ... 15}, step 0.1
In
100
2
1.5
185 Prot I start up threshold
{1,5 ... 15}, step 0.1
In
100
2
1.5
186 Prot I start up time
{0.10 ... 1.50}, step 0.01
s
100
2
0.1
187 Prot G configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4-15: not used
188 Prot G curve type
T=k | I
2
t = k
0 | 1
2
T=k
189 Prot G threshold T=k/I
2
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
190 Prot G time T=k/I
2
{0.01 … 1.00}, step 0.05
s
100
2
0.01
191 Prot G threshold T=k
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
192 Prot G time T=k
{0.01 … 1.00}, step 0.05
s
100
2
0.01
193 Prot G start up threshold
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
194 Prot G start up time
{0.01 … 1.00}, step 0.05
s
100
2
0.01
195 Prot G zone selectivity time
{0.04 ... 0.20}, step 0.01
s
100
2
0.04
196 Prot Ext G configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4-15: not used
197 Prot Ext G curve type
T=k | I
2
t = k
0 | 1
2
T=k
198 Prot Ext G threshold T=k/I
2
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
199 Prot Ext G time T=k/I
2
{0.01 … 1.00}, step 0.05
s
100
2
0.01
200 Prot Ext G threshold T=k
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
201 Prot Ext G time T=k
{0.01 … 1.00}, step 0.05
s
100
2
0.01
202 Prot Ext G start up threshold
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
203 Prot Ext G start up time
{0.01 … 1.00}, step 0.05
s
100
2
0.01
204 Prot Ext G zone selectivity time
{0.04 ... 0.20}, step 0.01
s
100
2
0.04
205 Prot U configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
206 Prot U threshold
{5 ... 90}, step 5
%
2
5
207 Prot U time
{0.5 ... 60}, step 0.5
s
100
2
0.5
208 Prot UV configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
209 Prot UV threshold
{0.50 ... 0.95}, step 0.01
Un
100
2
0.50
210 Prot UV time
{0.1 ... 5.0}, step 0.1
s
100
2
0.1
211 Prot OV configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
212 Prot OV threshold
{1.05 ... 1.20}, step 0.01
Un
100
2
1.05
213 Prot OV time
{0.1 ... 5.0}, step 0.1
s
100
2
0.1
214 Prot RV configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
215 Prot RV threshold
{0.10 ... 0.40}, step 0.05
Un
100
2
0.1
216 Prot RV time
{0.5 ... 30.0}, step 0.5
s
100
2
0.5
217 Prot RP configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
218 Prot RP threshold
{-0.10 ... -0.30}, step -0.02
Pnt
100
2
-0.10
219 Prot RP time
{0.5 ... 25.0}, step 0.1
s
100
2
0.5
220 Prot UF configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
221 Prot UF threshold
{0,90 ... 0.99}, step 0.01
Fn
100
2
0.9
222 Prot UF time
{0.5 ... 3.0}, step 0.1
s
100
2
0.5
223 Prot OF configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
224 Prot OF threshold
{1.01 ... 1.10}, step 0.01
Fn
100
2
1.01
225 Prot OF time
{0.5 ... 3.0}, step 0.1
s
100
2
0.5
226 Prot OT configuration
2
0: not used
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
227 Load control configuration
2
0: Iw Th enable/disable
Enable | Disable
0 | 1
1: LC1 Th enable/disable
Enable | Disable
0 | 1
2: LC2 Th enable/disable
Enable | Disable
0 | 1
3-15: not used
228 Warning current Iw
{0.30 ... 10.00}, step 0.05
In
100
2
0.30
229 LC1 threshold
{50 ... 100}, step 1
%I1
2
50
230 LC2 threshold
{50 ... 100}, step 1
%I1
2
50
231 Prot Rc configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
232 Prot Rc threshold
0.3 | 0.5 | 0.7 | 1.0 | 2.0 | 3.0
Idn
0 | 1 | 2 | 3 | 4 | 5
2
0.3
233 Prot Rc time
0.06 | 0.10 | 0.20 | 0.30 | 0.40 |
s
0 | 1 | 2 | 3 | 4 | 5
2
0.06
0.50 | 0.80 | 1.00 | 3.00 | 4.80
6 | 7 | 8 | 9
# Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
PR123 only
[bytes]
default