1SDH000510R0001
22/28
Page N.
L2388
EP010
ABB SACE
43 Loc Bus Relais 3 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
44 Loc Bus Relais 4 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm | LC1|
LC2 | Custom
45 Loc Bus Relais 4 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
46 Loc Bus Relais 6 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm | LC1|
LC2 | Custom
47 Loc Bus Relais 6 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
48 Loc Bus Relais 7 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm | LC1|
LC2 | Custom
49 Loc Bus Relais 7 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
50 Loc Bus Relais 8 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm | LC1|
LC2 | Custom
51 Loc Bus Relais 8 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
52 P relais Contact config
2
0: Relay P1
Not Latched | Latched
0 | 1
1: Relay P2
Not Latched | Latched
0 | 1
2: Relay P3
Not Latched | Latched
0 | 1
3: Relay P4
Not Latched | Latched
0 | 1
4: Contact P1
NO | NC
0 | 1
5: Contact P2
NO | NC
0 | 1
6: Contact P3
NO | NC
0 | 1
7: Contact P4
NO | NC
0 | 1
8-15: not used
53 P1 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm|LC1|
LC2 | Custom
54 P1 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
55 P2 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm| LC1|
LC2 | Custom
56 P2 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
57 P3 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm|LC1|
LC2 | Custom
58 P3 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
59 P4 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm| LC1|
LC2 | Custom
60 P4 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
61 Programmable Input config
Active High | Active Low
0 | 1
2 Active High
62 Programmable Input Function
Generic|External TRIP|Trip reset|
0 | 1 | 2 | 3 |
2 Generic
Set B (PR123 only) | Dial Local |
4 | 5 | 6
Reset Signalling Module|
Energy reset
63 Programmable Input Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
64 Data Logger Config
OFF | ON
0 | 1
2
OFF
65 Data Logger Trigger Type
None (free running)|Any Alarm|
0 | 1 | 2 | 3 |
L Timing | Any Trip | Custom
{256 ... 65535}
2
None
66 Data Logger Stop Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
67 Data Logger Frequency
600 | 1200 | 2400 | 4800
Hz
0 | 1 | 2 | 3
2
600
68 Cos
ϕ
Module Threshold
{0.50 ... 0.95}, step 0.01
100
2
0.5
Yes
69
CB TAG name 1
1 byte for char.
6
(ASCII)
70
CB TAG name 2
1 byte for char.
4
(ASCII)
71
User data 1
1 byte for char.
6
(ASCII)
72
User data 2
1 byte for char.
4
(ASCII)
73 Dual set CB close time
{0.20 ... 50.00}, step 0.10
s
100
2
0.20
Yes
74 Date of installation CB
Number of days from 31/12/1999
2
75 Date of last maint CB
Number of days from 31/12/1999
2
76 Port L configuration
2
0-3: not used
4: Thermal mem
OFF | ON
0 | 1
5-15: not used
77 Prot L curve type
I2t=k1|0,14/(i0.02-1)|13,5*b/(i-1)|
0 | 1 | 2 | 3
2
I2t = k1
80*b/(i2-1)
78
Prot L threshold
{0.40 ... 1.00}, step 0.01
In
100
2
0.4
79
Prot L time
{3 ... 144}, step 3
s
100
2
3
80
Prot L threshold IEC255
{0.40 ... 1.00}, step 0.01
In
100
2
0.4
81
Prot L time IEC255
{3 ... 144}, step 3
s
100
2
3
82
Prot S configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: not used
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4: Thermal mem
OFF | ON
0 | 1
# Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
PR123 only
[bytes]
default