1SDH000510R0001
17/28
Page N.
L2388
EP010
ABB SACE
1: Protection S electronic disable
Enabled | Disabled
0 | 1
Disabled
2: Protection S electronic curve type
Definite Time | Inverse Time
0 | 1
Inverse Time
3: Protection I electronic disable
Enabled | Disabled
0 | 1
Enabled
4: Protection G electronic disable
Enabled | Disabled
0 | 1
Disabled
5 15: not used
19 Product execution
LSI | LSIG | SI
0 | 1 | 2
2
LSI
Yes
20 Protection Unit serial number HI
1 byte for char.
8
Yes
(ASCII)
21 Protection Unit serial number LO
1 byte for char.
8
Yes
(ASCII)
22 CommunicationParameters bitfield:
2
Yes
0 - 7: Slave Address
{1 ... 247}
247
Yes
8: Baud rate
9600 | 19200
0 | 1
19200
Yes
9 - 10: parity
Even | Odd | None
00 | 01 | 10
Even
Yes
11: Addressing type
ABB | Standard
0 | 1
Standard
Yes
12 - 15: not used
Yes
23 System disconnection timeout
{0 ... 6000}, step 1
tenths of ms
2
100
Yes
24 Protection unit nominal current
100 | 150 | 160 | 200 | 250 |
A
2
100
Yes
300 | 320 | 400 | 600 | 630 |
800
25 CB type
T4 | T5 | S6
0 | 1 | 2
2
T4
Yes
26 Protection Unit SW version
MM.mm
MSB = MM
2
Yes
LSB = mm
27 Protection Unit version
PR222DS | PR222DS/PD
0 | 1
2
PR222DS/PD
Yes
#
Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
[bytes]
default
#
Name/Description
0
No device communication
1
Wrong device connected
2
Device not initialized
3
Internal configuration map error
4
Wrong parameter number
5
Wrong parameter value
6
Command not executed
7
I/O
8
Watchdog fault
9
Mo driver fault
10 RS 485 driver fault
11 NOT USED
12 NOT USED
13 NOT USED
14 NOT USED
15 NOT USED
DIAGNOSTIC
Number of variables 11
Number of bytes 2
3.1.3 Performance data and conditions
Trip Reports and Currents refresh rate
max. 2 [s]
Parameters refresh rate
max. 20 [s]