1SDH000510R0001
24/28
Page N.
L2388
EP010
ABB SACE
137 Prot RV time
{0.5 ... 30.0}, step 0.5
s
100
2
0.5
138 Prot RP configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
139 Prot RP threshold
{-0.10 ... -0.30}, step -0.02
Pnt
100
2
-0.10
140 Prot RP time
{0.5 ... 25.0}, step 0.1
s
100
2
0.5
141 Prot UF configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
142 Prot UF threshold
{0.90 ... 0.99}, step 0.01
Fn
100
2
0.9
143 Prot UF time
{0.5 ... 3.0}, step 0.1
s
100
2
0.5
144 Prot OF configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
145 Prot OF threshold
{1.01 ... 1.10}, step 0.01
Fn
100
2
1.01
146 Prot OF time
{0.5 ... 3.0}, step 0.1
s
100
2
0.5
147 Prot OT configuration
2
0: not used
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
148 Load control configuration
2
0: Iw Th enable/disable
Enable | Disable
0 | 1
1: LC1 Th enable/disable
Enable | Disable
0 | 1
2: LC2 Th enable/disable
Enable | Disable
0 | 1
3-15: not used
149 Warning current Iw
{0.30 ... 10.00}, step 0.05
In
100
2
0.30
150 LC1 threshold
{50 ... 100}, step 1
%I1
2
50
151 LC2 threshold
{50 ... 100}, step 1
%I1
2
50
152 Prot Rc configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
153 Prot Rc threshold
0.3 | 0.5 | 0.7 | 1.0 | 2.0 | 3.0
Idn
0 | 1 | 2 | 3 | 4 | 5
2
0.3
154 Prot Rc time
0.06 | 0.10 | 0.20 | 0.30 | 0.40 |
s
0 | 1 | 2 | 3 | 4 | 5
0.50 | 0.80 | 1.00 | 3.00 | 4.80
6 | 7 | 8 | 9
2
0.06
155 Prot L configuration
2
0-3: not used
4: Thermal mem
OFF | ON
0 | 1
5-15: not used
156 Prot L curve type
I2t = k1 | 0,14/(i0.02-1) |
0 | 1 | 2 | 3
2
I2t = k1
13,5*b/(i-1) | 80*b/(i2-1)
157 Prot L threshold
{0.40 ... 1.00}, step 0.01
In
100
2
0.4
158 Prot L time
{3 ... 144}, step 3
s
2
3
159 Prot L threshold IEC255
{0.40 ... 1.00}, step 0.01
In
100
2
0.4
160 Prot L time IEC255
{3 ... 144}, step 3
s
2
3
161 Prot S configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: not used
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4: Thermal mem
OFF | ON
0 | 1
5-15: not used
162 Prot S curve type
T=k | I
2
t = k
0 | 1
2
T=k
163 Prot S threshold T=k/I
2
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
164 Prot S time T=k/I
2
{0.05 … 0.8}, step 0.01
s
100
2
0.05
165 Prot S threshold T=k
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
166 Prot S time T=k
{0.05 … 0.8}, step 0.01
s
100
2
0.05
167 Prot S start up threshold
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
168 Prot S start up time
{0.10 ... 1.50}, step 0.01
s
100
2
0.1
169 Prot S zone selectivity time
{0.04 ... 0.20}, step 0.01
s
100
2
0.04
170 Prot S2 configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: not used
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4-15: not used
171 Prot S2 threshold T=k
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
172 Prot S2 time T=k
{0.05 … 0.8}, step 0.01
s
100
2
0.05
173 Prot S2 start up threshold
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
174 Prot S2 start up time
{0.10 ... 1.50}, step 0.01
s
100
2
0.1
175 Prot S2 zone selectivity time
{0.04 ... 0.20}, step 0.01
s
100
2
0.04
176 Prot D configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: not used
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4-15: not used
177 Prot D threshold
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
178 Prot D time Forward
{0.2 … 0.8}, step 0.01
s
100
2
0.2
179 Prot D time Backward
{0.2 … 0.8}, step 0.01
s
100
2
0.2
180 Prot D start up threshold
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
181 Prot D start up time
{0.10 ... 1.50}, step 0.01
s
100
2
0.1
182 Prot D zone selectivity time
{0.13 ... 0.50}, step 0.01
s
100
2
0.13
183 Prot I configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: not used
2: Start Up Th
OFF | ON
0 | 1
3-15: not used
# Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
PR123 only
[bytes]
default