1SDH000510R0001
16/28
Page N.
L2388
EP010
ABB SACE
5
L1 trip current
A | In
2
6
L2 trip current
A | In
2
7
L3 trip current
A | In
2
8
N trip current
A | In
2
9
Ground trip current
A | In
2
10 CB number of operations
2
11 CB number of protections trips
2
12 L number of trips
2
13 S number of trips
2
14 I number of trips
2
15 G number of trips
2
#
Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
[bytes]
default
#
Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
[bytes]
default
0
(Cyclic) Command info - value
No command | CB Open |
0 | 1 | 2 | 3 | 4
2
CB Close|CB reset|Trip Reset
1
(Cyclic) Command info - parameters
Don’t care
2
ANALOG OUTPUT
Number of variables 2
Number of bytes 4
#
Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
[bytes]
default
1
(Acyclic) Command info:
byte 0-1: command value
No Command | CB Open |
CB Close | CB Reset | Trip reset
0 | 1 | 2 | 3 | 4
2
0
byte 2-3: command parameter
Don’t care
2
0
2
Protection L manual trip level
{0.4 ...1}, step 0.02
In
100
2
0.4
Yes
3
Protection L manual trip delay
T4-320 | T5-630 | T5-600 UL: 3|
s
10
2
Yes
6 | 9 | 12
T4 - T5: 3 | 6 | 9 | 18
S6: 3 | 6 | 9 | 18
4
Protection S manual trip level
0 (Disabled) | 0.6 | 1.2 | 1.8 | 3 |
In
10
2
0
Yes
3.6 | 4.2 | 5.8 | 6.4 | 7 | 7.6 |
8.2 | 8.8 | 9.4 | 10
5
Protection S manual trip delay
0.05 | 0.1 | 0.25 | 0.5
s
100
2
0.05
Yes
6
Protection I manual trip level
T4-320 | T5-630 | T5-600 UL
In
10
2
0
Yes
0 (Disabled) | 1.5 | 2.5 | 3 | 4 |
4.5 | 5 | 5.5 | 6.5 | 7 | 7.5 | 8 | 9|
9.5 | 10 | 10.5
T4 - T5
0 (Disabled) | 1.5 | 2.5 | 3 | 4 |
4.5 | 5 | 5.5 | 6.5 | 7 | 7.5 | 8 | 9 |
9.5 | 10.5 | 12
S6
0 (Disabled) | 1.5 | 2.5 | 3 | 4 |
4.5 | 5 | 5.5 | 6.5 | 7 | 7.5 | 8 | 9 |
9.5 | 10.5 | 12
7
Protection G manual trip level
0 (Disabled) | 0.2 | 0.25 | 0.45 |
In
100
2
0
Yes
0.55 | 0.75 | 0.8 | 1
8
protection G manual trip delay
0.1 | 0.2 | 0.4 | 0.8
s
100
2
0.1
Yes
9
First bit field:
2
Yes
0: Neutral selection
50% | 100%
0 | 1
100%
Yes
1: Neutral enabling
Off (Disabled) | On (Enabled)
0 | 1
Off
Yes
2 : Protection S manual disable
Enabled | Disabled
0 | 1
Disabled
Yes
3: Protection S manual curve type
Definite Time | Inverse Time
0 | 1
Defifite Time
Yes
4: Protection I manual disable
Enabled | Disabled
0 | 1
Disabled
Yes
5: Protection G manual disable
Enabled | Disabled
0 | 1
Disabled
Yes
6 - 15: not used
Yes
10 date of test (DD/MM/YYY)
{1 ...31}, {1 ...12}, {0 ... 65535}
6
11 Protection L electronic trip level
{0.4 ... 1}, step 0.01
In
100
2
1
12 Protection L electronic trip delay
T4-320 | T5-630 | T5-600 UL:
s
10
2
18
{3 ...12}, step 0.5
T4 - T5: {3 ...18}, step 0.5
S6: {3 ...18}, step 0.5
13 Protection S electronic trip level
{0.6 ...10}, step 0.1
In
10
2
10
14 Protection S electronic trip delay
{0.05 ...0.5}, step 0.01
s
100
2
0.05
15 Protection I electronic trip level
T4-320 | T5-630 | T5-600 UL:
In
10
2
4
{1.5 ...10}, step 0.1
In
10
2
4
T4 - T5: {1.5 ...12}, step 0.1
S6: {1.5 ...12}, step 0.1
16 Protection G electronic trip level
{0.2 ...1}, step 0.01
In
100
2
1
17 Protection G electronic trip delay
{0.1 ... 0.8}, step 0.01
s
100
2
0.8
18 First bit field:
2
0: Prot. L electronic pre-alarm disable
Enabled | Disabled
0 | 1
Enabled
PARAMETERS
Number of parameters 27
Number of bytes 72