…Control
Loop 1 Split O/P*
The split output facility enables the
PID
control output (see page 30) to be split into 2 separate outputs. This enables heat
/ cool and other applications requiring dual outputs to be controlled. The linear relationship between the input from the
PID
algorithm and the 2 outputs is configured using the
Min
and
Max
Input / Output
parameters (see below).
When operating with
Split O/P
in
Manual
control mode, manual adjustment is made to the input at the split output block
(x axis). By default, the Operator page displays both output values (OP1 and OP2).
Loop 1 Time Prop
See
Basic
level, page 27.
*Applicable only if the output type selected is
Split O/P
– see page 36.
50
%
50
%
100
%
100
%
0
%
50
%
50
%
100
%
100
%
0
%
Output 1 (OP1)
Output 2 (OP2)
Max. Input 2 = 50
Max. Output 2 = 0
Min. Input 2 = 0
Min. Output 2 = 100
Max. Input 1 = 50
Min. Output 1 = 100
Max. Input 2 = 100
Max. Output 2 = 100
Min. Input 2 = 50
Min. Output 2 = 0
Min. Input 1 = 50
Min. Output 1 = 0
Split output
example
Min. Input 1 = 0
Min. Output 1 = 0
Max. Input 1 = 100
Max. Output 1 = 100
Input
Input
Ou
tp
u
t
Ou
tp
u
t
Heat / cool
example