ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/
8
,
1
/
4
and
1
/
2
DIN
7 Advanced Level
90
IM/CM/S–EN Rev. R
…Functions / …Real Time Alarms / …Real Time Alarm 1 (2)
On hour
Sets the hour the alarm is activated – not applicable if
Every Hour
(see page 89) is set to
On
.
On minute
Set the minutes past the hour the alarm is activated.
Duration
Set the duration the alarm is active.
Display enable
If disabled (
Off
), the alarm state does not appear in the operator level diagnostics window or
the alarm log
Tag
A 16-character alphanumeric tag displayed as a diagnostic message that appears in the
Diagnostic Status Bar
and the
Diagnostic View
in the
Operator Level
– see Section 5, page 22.
Bank Control
Bank control functionality allows a bank of output devices such as pumps, heaters or
fans to be scheduled
On
and
Off
under a duty / assist strategy.
If required one of two different wear levelling schedules can be selected, rotate or
FIFO
(
First In First Out
).
Up to 6 stages may be configured for bank control, each of which can be assigned to a
relay or digital output. Each stage has an associated
On
trip value,
Off
trip value and
initial Output
. All stages included in a wear levelling schedule must use the same
schedule type (
Rotate
or
FIFO
).
The example (overleaf) illustrates how the two modes operate to achieve wear levelling of
3 pumps in a duty / assist strategy.