ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/
8
,
1
/
4
and
1
/
2
DIN
10 Specification
IM/CM/S–EN Rev. R
113
Outputs
Controls / retransmission outputs
Relays
Digital input / output
2-Wire transmitter power supply
Number
2 (1 standard, 1 optional)
Type
Configurable as analog or digital pulse
Isolation
Galvanically isolated from the rest of the circuitry,
500 V for 1 minute
Analog range
0 to 20 mA programmable
Load 750
Max.
Accuracy
0.25 % of output or ± 10
µA
Number
CM10 / CM30: 4 (1 standard, 3 optional)
CM50: 4 (2 standard, 2 optional)
Type
CM10, CM30: Standard with changeover
contacts. Optional contacts selectable as N/O
or N/C (by jumper)
CM50: Selectable as N/O or N/C (by jumper)
Contact ratings
CM10:
CM30, CM50:
Relay 1:
5 A, 240 V
Relays 2, 3, 4: 5 A, 240 V (max. ambient
40 °C (104 °F)
Relays 2, 3, 4:
2 A, 240 V (max. ambient
55 °C (131 °F)
5 A, 240 V
Update rate
125 ms
CM10
2 (optional)
CM30 / CM50 6 (2 standard, 4 optional)
Type
User-programmable as input or output
Minimum input pulse duration – 125 ms
Input
–
volt-free or 24 V DC
–
1-signal: 15 to 30 V
–
0-signal: –3 to 5 V
–
Conforms to IEC 61131-2
Output
–
Open collector output
–
30 V, 100 mA max. switched
–
Conforms to IEC 61131-2
Update rate
125 ms
CM10
1 (standard)
CM30 / CM50
2 (1 standard, 1 optional)
Voltage
24 V DC
Drive
2 loops 45 mA max.