![ABB C1900RC Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/abb/c1900rc/c1900rc_operating-manual_3619931030.webp)
28
Increase
Proportional Band
P
I
D
Initial Settings
Observe response of process
Adjust the set point a small amount
Hold the set point at the new value until
the process begins to move
Reset the set point to the original value
Proportional Band = 100%
Integral Action Time = OFF
Derivative Action Time = OFF
Note Proportional Band value (PBc)
Measure the critical cycle time (tc)
P
2 x PBc
—
—
P+I
2.2 x PBc
tc/1.2
—
P+D
1.6 x PBc
tc/2
tc/12
Time
Pr
ocess V
a
riable
Response Time
•
•
•
•
•
•
•
•
Time
Pr
ocess V
a
riable
Response Time
Pr
ocess V
a
riable
Response Time
Critical
Cycle time (tcc)
Decrease
Proportional Band
Calculate Terms
P+I+D
1.6 x PBc
tc/2
tc/8
…5