Control unit
■
BCU control unit types
There are three variants of the BCU control unit used in ACS880: BCU-02, BCU-12 and
BCU-22. These have a different number of converter module connections (2, 7 and 12
respectively) but are otherwise identical. The three BCU types are interchangeable as long
as the number of connections is sufficient. For example, the BCU-22 can be used as a direct
replacement for both BCU-02 and BCU-12.
■
Replacing the memory unit
After replacing a control unit, you can retain the existing parameter settings by transferring
the memory unit from the defective control unit to the new control unit.
WARNING!
Do not remove or insert the memory unit when the control unit is powered.
1.
Stop the drive and do the steps in section
Electrical safety precautions (page 39)
before
you start the work.
2.
Make sure that the control unit is not powered.
3.
Undo the fastening screw and pull the memory unit out.
4.
Install a memory unit in reverse order.
■
Replacing the BCU control unit battery
Replace the real-time clock battery if the BATT OK LED is not illuminated when the control
unit is powered.
1.
Stop the drive and do the steps in section
Electrical safety precautions (page 39)
before
you start the work.
2.
Undo the fastening screw and remove the battery
3.
Replace the battery with a new BR2032 battery.
4.
Dispose of the old battery according to local disposal rules or applicable laws.
Maintenance 77
Содержание ACS880-1607LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 1607LC DC DC converter units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 32: ...32 ...
Страница 38: ...38 ...
Страница 60: ...60 ...
Страница 80: ...80 ...
Страница 90: ...90 ...
Страница 102: ...Unit with 1 R8i converter module 102 Dimension drawings ...
Страница 103: ...Dimension drawings 103 ...
Страница 104: ...Location and size of energy storage connection terminals 104 Dimension drawings ...