A cable entry example with 360 degrees grounding of
the shield.
4
5
■
Connection procedure of the load disconnected indicator cable
WARNING!
Obey the safety instructions given in
Safety instructions for ACS880
liquid-cooled multidrive cabinets and modules
(3AXD50000048633
[English]). If you ignore the safety instructions, injury or death, or damage
to the equipment can occur.
If you are not a qualified electrician, do not do installation or maintenance
work.
1.
Stop the drive and do the steps in section
Electrical safety precautions (page 39)
before
you start the work.
2.
Open the door of the DC/DC converter cubicle and remove the shrouding.
3.
Run the load disconnected indicator cable inside the cubicle and connect to the
appropriate terminal. Obey the general control cable connection instructions. See section
Connecting the control cables (page 43)