Default I/O diagram of the converter control unit
The diagram below shows the default I/O connections on the converter control unit, and
describes the use of the signals/connections. Under normal circumstances, the factory-made
wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 …
2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
XD2D
Drive-to-drive link
1
B
Drive-to-drive link (not in use by default)
2
A
3
BGND
4
Shield
X485
RS485 connection
B
CIO-01 connection (optional)
A
BGND
Shield
XRO1…XRO3
Relay outputs
11
NC
XRO1: Not in use
250 V AC / 30 V DC / 2 A
12
COM
13
NO
21
NC
XRO2:
Fault(-1)
1)
(Energized = no fault)
250 V AC / 30 V DC / 2 A
22
COM
23
NO
31
NC
XRO3:
Fan control
(DC/DC converter running, fan control on)
250 V AC / 30 V DC / 2 A
32
COM
33
NO
XSTO
XSTO connector
1
OUT
XSTO connector. Both circuits (power module, control unit) must be closed for
the unit to start. (IN1 and IN2 must be connected to OUT.)
6)
2
SGND
3
IN1
4
IN2
5
IN1
Not in use
6
SGND
7
IN2
8
SGND
XDI
Digital inputs
1
DI1
Temp fault
1)
(0 = overtemperature)
2
DI2
Not in use by default.
3
DI3
4
DI4
5
DI5
6
DI6
7
DIIL
XDIO
Digital input/outputs
1
DIO1
Not in use by default
2
DIO2
Not in use by default
3
DIOGND
Digital input/output ground
4
DIOGND
Digital input/output ground
XD24
Auxiliary voltage output
5
+24VD
+24 V DC 200 mA
4)
6
DICOM
Digital input ground
7
+24VD
+24 V DC 200 mA
4)
8
DIOGND
Digital input/output ground
DICOM=DIOGND Ground selection switch
5)
XAI
Analog inputs, reference voltage output
1
+VREF
10 V DC,
R
L
1…10 kohm
2
-VREF
-10 V DC,
R
L
1…10 kohm
3
AGND
Ground
4
AI1+
Not in use by default.
0(2)…10 V,
R
in
> 200 kohm
2)
5
AI1-
6
AI2+
Not in use by default.
0(4)…20 mA,
R
in
= 100 ohm
3)
7
AI2-
XAO
Analog outputs
1
AO1
Zero
1)
0…20 mA,
R
L
< 500 ohm (not in use by default)
2
AGND
3
AO2
Zero
1)
0…20 mA,
R
L
< 500 ohm (not in use by default)
4
AGND
XPOW
External power input
1
+24VI
24 V DC, 2.05 A
2
GND
3
+24VI
4
GND
X12
Safety functions module connection
(not in use in DDC)
X13
Control panel connection
X205
Memory unit connection
7
8
5
6
54 Control units of the drive
Содержание ACS880-1607LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 1607LC DC DC converter units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 32: ...32 ...
Страница 38: ...38 ...
Страница 60: ...60 ...
Страница 80: ...80 ...
Страница 90: ...90 ...
Страница 102: ...Unit with 1 R8i converter module 102 Dimension drawings ...
Страница 103: ...Dimension drawings 103 ...
Страница 104: ...Location and size of energy storage connection terminals 104 Dimension drawings ...