Description
Example value
Name
Index
Selects the fault reaction in case the drive
modulation is lost during the SLS decelera-
tion ramp, when SLS is activated from
speed which is higher than SLS limit speed.
Modoff delay time
SLS ramp modoff re-
action
SLSx.05
For more information, see FSO module
user's manual.
Time to trip when modulation is lost.
0 ms
SLS ramp modoff
delay time
SLSx.06
Note:
SLSx.06 time must be set shorter
than STO.14, otherwise STO is not activ-
ated due to limit hit when drive modulation
is lost with SLS function.
Note:
If encoder feedback is in use,
SLSx.06 parameter has no effect.
Sets the digital input that is connected to
the primary input of the SLS function with
limits 1.
DI X113:4 & X114:4
SLS1 input A
SLSx.11
For the Q965, ABB has configured
the SLS request signal to these digital in-
puts at the factory.
Note:
The default value after factory reset
is
None
.
Always check this parameter after factory
reset.
Sets the SLS1 negative speed limit that trips
the drive.
-250 rpm
SLS1 trip limit negat-
ive
SLSx.13
Adjust the default value to meet the motor
in use.
Note:
The difference between the SLS trip
limit and the corresponding SLS limit
(200.22) must be at least 0.1 rpm.
Note:
The default value after factory reset
is
0
rpm.
Always check this parameter after factory
reset.
Sets the SLS1 positive speed limit that trips
the drive.
250 rpm
SLS1 trip limit posit-
ive
SLSx.14
Adjust the default value to meet the motor
in use.
Note:
The difference between the SLS trip
limit and the corresponding SLS limit
(200.23) must be at least 0.1 rpm.
Note:
The default value after factory reset
is
0
rpm.
Always check this parameter after factory
reset.
40 Option description